User manual
Diagnostics and Troubleshooting MVI56-HART ♦ ControlLogix Platform
User Manual HART Multi-drop Master Communication Module
Page 68 of 171 ProSoft Technology, Inc.
October 13, 2011
Opening the Data Analyzer Menu
Press [A] to open the Data Analyzer Menu. Use this command to view all bytes of data
transferred on each port. Both the transmitted and received data bytes are displayed.
Refer to Data Analyzer (page 70) for more information about this menu.
Important: When in analyzer mode, program execution will slow down. Only use
this tool during a troubleshooting session. Before disconnecting from the
Config/Debug port, please press [S]
to stop the data analyzer, and then press
[M]
to return to the main menu. This action will allow the module to resume its
normal high speed operating mode.
Viewing the Slave Status List
Press [V] to view the slave status values associated with the ports. The slave status
values are defined as follows:
ERR = Device in Error
OK = Device OK
[Blank] = Device Not Polled.
Opening the Command Error List Menu
Press [E], [F], [G] or [H] to open the Command Error List for clients 1 through 4
respectively. This list consists of multiple pages of command list error/status data. Press
[?] to view a list of commands available on this menu.
Opening the Command List Menu
Press [N], [O], [P] or [Q] to open the Command List menu for clients 1 through 4
respectively. Use this command to view the configured command list for the module.
Viewing the Master Command List Help
Press [H] to view a help screen with explanations of each item that appears on the
command list.