3.1.4 Auto-Poll Data (HARTAutoPoll)
Auto-Poll Data (HARTAutoPoll)
This data object contains the auto-poll data ready to be used by the user (multi-drop or
point-to-point). First define where the auto-poll data will copied to in the MVI56-HART
database using the DB AutoPoll Address parameter in the configuration file. Then copy
the data from the MVI56-HART database into the CLX memory (HARTAutoPoll object)
using the ladder logic.
Name Data Type Description
Auto_Poll_CMD_Status SINT Auto-Polling command status bits
Last_Status_Byte SINT Last first status byte received from device
Last_Second_Status_Byte SINT Last second status byte received from device
Manufacture_ID_Code SINT Device's manufacture ID Code
Device_Type_Code SINT Device Type Code
Min_Preambles SINT Minimum Number of Preambles
Universal_CMD_Major SINT Universal Command Major Rev#
Device_Rev_Level SINT Device Revision Level
Software_Rev_Level SINT Software Revision Level
Hardware_Rev_Level SINT Hardware Revision Level
Device_Flags SINT Device Flags
Device_ID SINT[3] Device ID
Min_Preambles_Resp SINT Minimum Preambles Count to Response
Max_Number_Devices SINT Maximum Number of HART Devices in the network
Config_Change_Count INT Counter for configuration change
Ext_Dev_Status SINT Extended Field Device Status
Primary_Var_Units SINT Primary Units Code
Secondary_Var_Units SINT Secondary Units Code
Tertiary_Var_Units SINT Tertiary Units Code
Quaternary_Var_Units SINT Quaternary Units Code
Tag_Name SINT[8] HART device Tag Name
Descriptor SINT[16] HART device Descriptor
Tag_Descriptor_Data SINT[3] HART device descriptor data
Transd_Serial_Num SINT[3] Transducer Serial Number
Transd_limits SINT Transducer limits
PV_Alarms SINT PV Alarm counter
PV_Transfer SINT PV Transfer counter
PV_URLLRV_Units SINT PV upper and lower range value limits