User manual

Reference MVI56-HART ♦ ControlLogix Platform
User Manual HART Multi-drop Master Communication Module
Page 128 of 171 ProSoft Technology, Inc.
October 13, 2011
COMMAND 17 - Write Message
Description
This command writes an ASCII message contained in the HART Device and that can be
read with command 12.
Write Parameters
Word High Byte Low Byte
0 Packed ASCII Message Byte 0 Packed ASCII Message Byte 1
1 Packed ASCII Message Byte 2 Packed ASCII Message Byte 3
.
.
.
.
.
.
11 Packed ASCII Message Byte 22 Packed ASCII Message Byte 23
Floating Point Data Returned
NONE
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD