User manual
MVI56-HART ♦ ControlLogix Platform Reference
HART Multi-drop Master Communication Module User Manual
ProSoft Technology, Inc. Page 125 of 171
October 13, 2011
COMMAND 14 - Read PV Sensor Info
Description
This command gets information about the Primary Variable sensor, like limits and span.
Write Parameters
NONE
Floating Point Data Returned
Word High Byte Low Byte
0 Upper Sensor Limit
1
2 Lower Sensor Limit
3
4 Minimum Span
5
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 Sensor Serial Number 0 Sensor Serial Number 1
2 Sensor Serial Number 2 Unit Codes for Sensor Limits and Span