User manual

Reference MVI56-HART ♦ ControlLogix Platform
User Manual HART Multi-drop Master Communication Module
Page 122 of 171 ProSoft Technology, Inc.
October 13, 2011
COMMAND 06 - Write Polling Address
Description
This command sets the polling address of a HART device. Extreme care should be taken
when you use this command because you can loose the communication with the device.
Write Parameters
Word High Byte Low Byte
0 Polling Address Polling Address
Floating Point Data Returned
NONE
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 Polling Address 0