User manual
Publication LOGIX-AP010B-EN-P - May 2010 23
Controllers and I/O Modules Chapter 1
Analog Input/Output
Modules
When converting from a Siemens S5 Controller to a Rockwell Automation
Logix Controller, it is essential to choose analog input/output modules that
will be compatible with existing analog input/output devices.
Some of the S5-135U and S5-155U analog input modules are used in
conjunction with range cards, with range cards being used depending on the
type of signal being produced by the analog input device as shown in the
following tables.
Siemens S5 Analog Input Modules
Cat. No. Channels Range / Sensor
460-4UA13 8 – single See range cards
465-4UA12 16 – voltage/current
8 – Pt100 resistance
See range cards
465-4UA13 16 – voltage/current
8 – Pt100 resistance
See range cards
463-4UA12 4 – single 0…1V, 10V, 20 mA
463-4UB12 4 – single 4…20 mA
466-3LA11 16 – voltage/current
8 – Pt100 resistance
0…1.25V, 2.5V, 5V, 10V
466-4LA11 16 – voltage/current
8 – Pt100 resistance
0…20 mA
4…20 mA
Siemens S5 Analog Input Range Cards
Cat. No. Range Cards Range / Sensor
460-4UA13 498-1AA11 ±12.5, 50, 500 mV, Pt100
465-4UA12 498-1AA11 ± 50/500 mV, Pt100
498-1AA21 ± 1V
465-4UA13 498-1AA31 ± 10V
498-1AA41 ± 20 mA
498-1AA51 4…20 mA
498-1AA61 ± 5V
498-1AA71 4…20 mA