User manual

20 Publication LOGIX-AP010B-EN-P - May 2010
Chapter 1 Controllers and I/O Modules
These are the available ControlLogix Digital AC Input Modules.
Replacing 6ES5 435-4UA12 DI Modules
These modules have an operating voltage range of 24…60V AC and the
nearest equivalent ControlLogix module is the 1756-IN16 that has an
operating range of 10…30V AC.
The actual values of input voltage presented by the input signals should be
reviewed and if they are all found to be within the range 10…30V AC then the
6ES5 435-4UA12 DI module can be replaced by the ControlLogix 1756-IN16
module. There is no ControlLogix DI module that operates with an input
voltage in the range 30…60V AC.
Replacing 6ES5 436-4UA12 DI Modules
These modules could be replaced by a ControlLogix module 1756-IA16, or if
individually isolated inputs are required, then the ControlLogix module
1756-IA16I can be used.
Two 16-channel 6ES5 436-4UA12 modules could be replaced by one 32-input
channel 1756-IA32 module.
Replacing 6ES5 436-4UB12 DI Modules
These modules could be replaced by the ControlLogix module 1756-IA8D
with individual diagnostic information for each input channel.
Two 8-channel 6ES5 436-4UB12 modules could be replaced by one 16-input
channel 1756-IA16 module.
ControlLogix Digital AC Input Modules
Cat. No. Inputs Voltage
1756-IN16 16
10
30V AC
1756-IA8D 8
79
132V AC
1756-IA16 16
79
132V AC
1756-IA16I 16
79
132V AC
1756-IA32 32
79
132V AC
1756-IM16I 16
79
132V AC