COMMAND 35: Write Range Values
Description:
This command writes the Upper and Lower range of the Primary Variable
Write Parameters:
WORD HIGH BYTE LOW BYTE
0 Range Units Code Floating Point Upper Range Value (Byte 0)
1 Floating Point Upper Range Value (Byte 1) Floating Point Upper Range Value (Byte 2)
2 Floating Point Upper Range Value (Byte 3) Floating Point Lower Range Value (Byte 0)
3 Floating Point Lower Range Value (Byte 1) Floating Point Lower Range Value (Byte 2)
4 Floating Point Lower Range Value (Byte 3)
Floating Point Data Returned:
WORD HIGH BYTE LOW BYTE
0
1
Upper Range Value
2
3
Lower Range Value
Integer Data Returned:
WORD HIGH BYTE LOW BYTE
0 STATUS WORD
1 Range Units Code 0