Specifications

ProLinx Communication Gateways, Inc. 41
HART Master Protocol Drive Manual
August 17, 2004
COMMAND 15: Read Output Information
Description:
This command gets information about the Primary Variable Output Information.
Write Parameters:
NONE
Floating Point Data Returned:
WORD HIGH BYTE LOW BYTE
0
1
Upper Range Value
2
3
Lower Range Value
4
5
Damping Value (Sec)
Integer Data Returned:
WORD HIGH BYTE LOW BYTE
0 STATUS WORD
1 Alarm Select Code Transfer Function Code
2 Primary Variable Range Units Code Write-Protect Code
2 Private-Label Distributor Code 0