Specifications

ProLinx Communication Gateways, Inc. 37
HART Master Protocol Drive Manual
August 17, 2004
COMMAND 06: Write Polling Address
Description:
This command sets the polling address of a HART device. Extreme care should
be taken when you use this command because you can loose the communication
with the device.
Write Parameters:
WORD HIGH BYTE LOW BYTE
0 Polling Address
Floating Point Data Returned:
NONE
Integer Data Returned:
WORD HIGH BYTE LOW BYTE
0 STATUS WORD
1 Polling Address 0