Specifications
ProLinx Communication Gateways, Inc. 24
HART Master Protocol Drive Manual
August 17, 2004
6 Error/Status Data
The module error/status data areas are discussed in this section. The module contains
three areas related to this data. The user defines the location of these data sets in the
virtual database of the module. The error/status data contains module data, the six
command error list data sets contain the errors associated with each respective
command list and the four slave status list tables contain the communication status of
each port's slave devices.
6.1 Viewing Error and Status Data
The following sections list the register addresses that contain error and status data. You
use the Database View option to view the contents of these registers. Refer to the
ProLinx Communication Gateways, Inc. Startup Guide for detailed information on viewing
error and status registers.
6.2 Configuration Error Word Table
HART CONFIGURATION ERROR WORD
Bit Code Description
0 0x0001 Enabled not set to Y or N
1 0x0002 Enable Handheld not set to Y or N
2 0x0004 Primary Master not set to Y or N
3 0x0008 Invalid Preambles (1 to 50)
4 0x0010 Invalid Short Address Retries (0 to 50)
5 0x0020 Invalid Long Address Retries (0 to 50)
6 0x0040 Invalid Retries After Error (0 to 50)
7 0x0080 Invalid Poll Time After Error (0 to 10000)
8 0x0100 Invalid DB Address Status
9 0x0200 Invalid Command Count
10 0x0400 Memory Error in allocating commands
11 0x0800 Memory Error in allocating command fixed data
12 0x1000 Memory Error in allocating TX/RX buffers
13 0x2000 HART Board not found
14 0x4000 Cannot initialize HART channel
15 0x8000 reserved