Specifications

HART ProLinx Gateway Reference
HART Master Driver Manual
Page 64 of 119 ProSoft Technology, Inc.
July 7, 2009
5.2 HART Common Practice Commands
COMMAND 33 - Read Transmitter Variables
Description
This command gets four user selected dynamic Variables.
Write Parameters
Word High Byte Low Byte
0 Transmitter Variable Code For Slot 0 Transmitter Variable Code For Slot 1
1 Transmitter Variable Code For Slot 2 Transmitter Variable Code For Slot 3
Floating Point Data Returned
Word High Byte Low Byte
0
1
Variable for Slot 0
2
3
Variable for Slot 0
4
5
Variable for Slot 2
6
7
Variable for Slot 3
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 Transmitter Variable Code For Slot 0 Units Code for Slot 0 Variable
2 Transmitter Variable Code For Slot 1 Units Code for Slot 1 Variable
3 Transmitter Variable Code For Slot 2 Units Code for Slot 2 Variable
4 Transmitter Variable Code For Slot 3 Units Code for Slot 3 Variable