Specifications
ProLinx-HART ♦ ProLinx Gateway Reference
HART Master with Analog I/O Driver Manual
ProSoft Technology, Inc. Page 89 of 104
October 13, 2011
Bit 7 of First Byte = 0
Command Error
Bit 2 Analog Output Saturated
Bit 1 Variable (not Primary) Out Of Limits
Bit 0 Primary Variable Out of Limits
Command Specific Errors
8 Update Failed
Update In Progress
Set to Nearest Possible Value
9 Applied Process Too High
Lower Range Value Too High
Not in Fixed Current Mode
10 Applied Process Too Low
Lower Range Value Too Low
Multi-drop Not Supported
11 In Multi-drop Mode
Invalid Transmitter Variable Code
Upper Range Value Too High
12 Invalid Unit Code
Upper Range Value Too Low
13 Both Range Values Out of Limits
14 Pushed Upper Range Value Over Limit
Span Too Small
HART Configuration Error Word
Bit Code Description
0 0x0001 Enabled not set to Y or N
1 0x0002 Enable Handheld not set to Y or N
2 0x0004 Primary Master not set to Y or N
3 0x0008 Invalid Preambles (1 to 50)
4 0x0010 Invalid Short Address Retries (0 to 50)
5 0x0020 Invalid Long Address Retries (0 to 50)
6 0x0040 Invalid Retries After Error (0 to 50)
7 0x0080 Invalid Poll Time After Error (0 to 10000)
8 0x0100 Invalid DB Address Status
9 0x0200 Invalid Command Count
10 0x0400 Memory Error in allocating commands
11 0x0800 Memory Error in allocating command fixed data
12 0x1000 Memory Error in allocating TX/RX buffers
13 0x2000 HART Board not found
14 0x4000 Cannot initialize HART channel
15 0x8000 reserved