Specifications

ProLinx-HART ♦ ProLinx Gateway Reference
HART Master with Analog I/O Driver Manual
ProSoft Technology, Inc. Page 57 of 104
October 13, 2011
COMMAND 35 - Write Range Values
Description
This command writes the Upper and Lower range of the Primary Variable
Write Parameters
Word High Byte Low Byte
0 Range Units Code Floating Point Upper Range Value (Byte 0)
1 Floating Point Upper Range Value (Byte 1) Floating Point Upper Range Value (Byte 2)
2 Floating Point Upper Range Value (Byte 3) Floating Point Lower Range Value (Byte 0)
3 Floating Point Lower Range Value (Byte 1) Floating Point Lower Range Value (Byte 2)
4 Floating Point Lower Range Value (Byte 3) Floating Point Lower Range Value (Byte 3)
Floating Point Data Returned
Word High Byte Low Byte
0 Upper Range Value
1
2 Lower Range Value
3
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 Range Units Code 0