Specifications

Reference ProLinx-HART ♦ ProLinx Gateway
Driver Manual HART Master with Analog I/O
Page 48 of 104 ProSoft Technology, Inc.
October 13, 2011
COMMAND 13 - Read Tag, Descriptor and Date
Description
This command reads an ASCII Tag which identifies the device, an ASCII descriptor of the
device and the last Date it has been configured.
Write Parameters
NONE
Floating Point Data Returned
NONE
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 TAG ASCII Character 0 TAG ASCII Character 1
2 TAG ASCII Character 2 TAG ASCII Character 3
3 TAG ASCII Character 4 TAG ASCII Character 5
4 TAG ASCII Character 6 TAG ASCII Character 7
5 Descriptor ASCII Character 0 Message ASCII Character 1
.
.
.
.
.
.
12 Descriptor ASCII Character 14 Message ASCII Character 15
13 Date Date
14 Date 0