With the auto-poll feature enabled, the module automatically generates the following
HART commands and stores the data in the module's database at the user-specified
location:
CMD Description
0 Read Unique Identifier
3 Read Current and Four Dynamic Variables
13 Read Tag, Descriptor and Date
14 Read PV Sensor Information
15 Read Output Information
If the unit is set for point-to-point mode, the module will automatically gather the
information for the device with the polling address (short address) of zero and place the
data into the database. Each device requires a 50-word database area with the format
shown in the following table.
DB Byte
Offset
Type Description Byte
Cnt
Data
Source
Use of Data
0 byte Auto-polling command status bits 1 App Status
1 byte Last first status byte received from
device
1 Resp Status
2 byte Last second status byte received
from device
1 Resp Status
3 byte Manufacture ID Code 1 CMD 0 LongAddress
4 byte Device Type Code 1 CMD 0 LongAddress
5 byte Minimum number of preambles 1 CMD 0 Msgconstruction
6 byte Universal Command Major Rev # 1 CMD 0 Msgchoice
7 byte Device Revision Level 1 CMD 0 Info
8 byte Software Revision Level 1 CMD 0 Info
9 byte Hardware Revision Level/Physical
Signaling Code
1 CMD 0 Info
10 byte Device Flags 1 CMD 0 Info
11 to 13 byte Device ID 3 CMD 0 Long Address
14 byte Minimum number of preambles to
be sent with the response message
from the slave to the master.
1 CMD 0
15 byte Maximum number of device
variables
1 CMD 0 Info
16 to 17 word Configuration Change Counter 2 CMD 0 Info
18 byte Extended Field Device Status 1 CMD 0 Info
19 byte Primary variable units code 1 CMD 3 Cfg
20 byte Secondary variable units code 1 CMD 3 Cfg
21 byte Tertiary variable units code 1 CMD 3 Cfg
22 byte Quaternary variable units code 1 CMD 3 Cfg
23 to 30 byte Tag name 8 CMD 13 Info
31 to 46 byte Descriptor 16 CMD 13 Info
47 to 49 byte Tag/Descriptor data 3 CMD 13 Info
50 to 52 byte Transducer serial number 3 CMD 14 Info