ProLinx-HART ProLinx Gateway HART Master with Analog I/O October 13, 2011 DRIVER MANUAL
Your Feedback Please We always want you to feel that you made the right decision to use our products. If you have suggestions, comments, compliments or complaints about our products, documentation, or support, please write or call us. How to Contact Us ProSoft Technology 5201 Truxtun Ave., 3rd Floor Bakersfield, CA 93309 +1 (661) 716-5100 +1 (661) 716-5101 (Fax) www.prosoft-technology.com support@prosoft-technology.com Copyright © 2011 ProSoft Technology, Inc., all rights reserved.
Important Installation Instructions Power, Input, and Output (I/O) wiring must be in accordance with Class I, Division 2 wiring methods, Article 501-4 (b) of the National Electrical Code, NFPA 70 for installation in the U.S., or as specified in Section 18-1J2 of the Canadian Electrical Code for installations in Canada, and in accordance with the authority having jurisdiction.
PLX Markings Label Markings ATEX II 3 G Ex nA IIC T4 -20°C <= Ta <= 50°C II – Equipment intended for above ground use (not for use in mines). 3 – Category 3 equipment, investigated for normal operation only. G – Equipment protected against explosive gasses.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Contents Driver Manual Contents Your Feedback Please ........................................................................................................................ 2 How to Contact Us .............................................................................................................................. 2 ® ProSoft Technology Product Documentation ....................................................................................
Contents Driver Manual 3.4 3.5 4 ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 3.3.3 3.3.4 3.3.5 3.3.6 3.3.7 3.3.8 3.3.9 3.3.10 3.3.11 3.3.12 3.3.13 3.3.14 3.3.15 3.3.16 3.3.17 3.3.18 3.3.19 3.4.1 3.4.2 3.4.3 3.4.4 3.4.5 3.4.6 Reference Enable ..................................................................................................................... 32 Float DB Address ....................................................................................................
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Contents Driver Manual COMMAND 44 - Write PV Units .................................................................................................. 66 COMMAND 45 - Trim DAC Zero ................................................................................................. 67 COMMAND 46 - Trim DAC Gain ................................................................................................. 68 COMMAND 47 - Write Transfer Function .....
Contents Driver Manual Page 8 of 104 ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O ProSoft Technology, Inc.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 1 Start Here Driver Manual Start Here In This Chapter System Requirements ........................................................................... 10 Package Contents ................................................................................. 11 Mounting the Gateway on a DIN-rail ..................................................... 12 Connecting Power to the Unit ...........................................................
Start Here Driver Manual 1.1 ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O System Requirements The ProSoft Configuration Builder configuration software for the ProLinx-HART module requires the following minimum hardware and software components: ® Pentium II 450 MHz minimum.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 1.2 Start Here Driver Manual Package Contents The following components are included with your ProLinx-HART module, and are all required for installation and configuration. Important: Before beginning the installation, please verify that all of the following items are present. Qty.
Start Here Driver Manual 1.3 ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Mounting the Gateway on a DIN-rail ProLinx 5000/6000 Series module Page 12 of 104 ProSoft Technology, Inc.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 1.4 Start Here Driver Manual Connecting Power to the Unit WARNING: Ensure that you do not reverse polarity when applying power to the module. This will cause damage to the module’s power supply. ProSoft Technology, Inc.
Start Here Driver Manual 1.5 ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Installing ProSoft Configuration Builder Software You must install the ProSoft Configuration Builder (PCB) software to configure the module. You can always get the newest version of ProSoft Configuration Builder from the ProSoft Technology website. To install ProSoft Configuration Builder from the ProSoft Technology website 1 Open your web browser and navigate to http://www.prosoft-technology.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 2 Functional Overview Driver Manual Functional Overview In This Chapter HART Channels .................................................................................... 16 Functional Specifications - HART Analog .............................................. 17 Module Internal Database .....................................................................
Functional Overview Driver Manual 2.1 ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O HART Channels The ProLinx module supports the HART protocol as a Master on up to 4 channels per interface card, with one or two cards per gateway. Each channel is individually configurable.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 2.2 Functional Overview Driver Manual Functional Specifications - HART Analog The HART Analog Protocol exists in 4 and 8 channel implementations. This driver can be configured on an individual channel basis to operate as a HART Master Station and supports all the available HART commands including Universal, Common Practice and Device Specific Commands.
Functional Overview Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O HART Commands supported Universal Command Set 00 01 02 03 06 11 12 13 14 15 16 17 18 19 Page 18 of 104 Read Unique Identifier Read Primary Variable Read Current And Percent Of Range Read Dynamic Variables Write Polling Address Read Unique Identifier Associated With Tag Read Message Read Tag Descriptor Date Read PV Sensor Info Read Output Information Read Final Assembly Number Write Message Write Tag Descriptor D
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Functional Overview Driver Manual Common Practice Command Set 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 108 109 110 Read Transmitter Variables Write Damping Value Write Range Values Set Upper Range Value Set Lower Range Value Reset Configuration Changed Flag EEprom Control Enter Exit Fixed Current Mode Perform Transmitter Self Test Perform Master Reset Set Pv Zero Write Pv Units Trim Dac Zero Trim Dac Gain W
Functional Overview Driver Manual 2.3 ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Module Internal Database The internal database is central to the functionality of the module. This database is shared between all the ports on the module and is used as a conduit to pass information from one device on one network to one or more devices on another network. This permits data from devices on one communication port to be viewed and controlled by devices on another port.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Functional Overview Driver Manual 2.3.2 HART Command List The HART Command List specifies the commands to be executed to the HART devices connected to a channel. A HART command can be seen as an outgoing message to the HART devices that provides Write Data for a specific command or a response message that carries process data (Read Data) back to the module.
Functional Overview Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O With the auto-poll feature enabled, the module automatically generates the following HART commands and stores the data in the module's database at the user-specified location: CMD Description 0 Read Unique Identifier 3 Read Current and Four Dynamic Variables 13 Read Tag, Descriptor and Date 14 Read PV Sensor Information 15 Read Output Information If the unit is set for point-to-point mode, the module w
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Functional Overview Driver Manual DB Byte Offset Type Description Byte Cnt Data Source Use of Data 53 byte Transducer limits and min span units code 1 CMD 14 Info 54 byte PV alarm selection code 1 CMD 15 Info 55 byte PV transfer function code 1 CMD 15 Info 56 byte PV upper and lower range value units code 1 CMD 15 Info 57 byte Write protection code 1 CMD 15 Status 58 byte Private label distributor code 1 CMD
Functional Overview Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O The following topics describe the modes of module operation. Auto-Poll Disabled Mode If the auto-polling feature is disabled (Auto-Poll Code = N), the module functions as shown in the following diagram: Only the user commands are executed and all data is placed in and sourced from the module's internal database.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Functional Overview Driver Manual When the point-to-point mode of auto-polling is enabled (Auto-Poll Code = P), the following diagram applies to the channel operation: ProSoft Technology, Inc.
Functional Overview Driver Manual Page 26 of 104 ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O ProSoft Technology, Inc.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 3 HART Protocol Configuration Driver Manual HART Protocol Configuration In This Chapter [Analog HART Card x] ........................................................................... 28 [HART PORT x] ..................................................................................... 29 [HART PORT x COMMANDS] ............................................................... 31 Using the CommonNet Data Map .........................
HART Protocol Configuration Driver Manual 3.1 ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O [Analog HART Card x] 3.1.1 Database Register -1, 0 to 3984 This parameter sets the database address in the module where the following values will be placed: Digitized values (4 Registers) Counters (4 Registers) Scaled values (8 Registers, 4 floating values) Counters are incremented, usually about 15 times per second, to show the number of times digital values have been scaled.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 3.2 HART Protocol Configuration Driver Manual [HART PORT x] The configuration file sections [HART PORT 0] through [HART PORT 3] (for 4 channel modules) or [HART PORT 0] through [HART PORT 7] (for 8 channel modules) set HART channel communication parameters, define the protocol specific parameters, and set the command list parameters. The parameters are the same for all channels.
HART Protocol Configuration Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 3.2.6 Command Count 0 to 99 This parameter sets the number of user commands to be utilized. The first command in the list is always reserved for the auto-poll command so the user should configure this value considering one command for the auto-poll. For example, if the user configures two commands, the command count parameter should be set as 3. This parameter can be set from 0 to 99.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 3.3 HART Protocol Configuration Driver Manual [HART PORT x COMMANDS] The [HART PORT x COMMANDS] sections of the configuration file contain the userdefined HART command lists for each channel. The commands in these lists are sent to slave devices attached to the HART channels. The module supports up to 100 commands per channel. 3.3.1 Command List Overview The ProLinx-HART module uses a command list to interface with HART slave devices.
HART Protocol Configuration Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 3.3.2 HART Command Entry Formats Refer to the Reference (page 41, page 42, page 30) chapter for a complete discussion of the HART commands supported by the module, and the structure and content of the data returned for each command. The following illustration shows a command list section of the configuration file: 3.3.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O HART Protocol Configuration Driver Manual 3.3.4 Float DB Address 0 to 3998 This field specifies the internal database register where the floating point values returned by the command will be placed. 3.3.5 Poll Interval 0 TO 65535 This parameter specifies the minimum interval between executions of a continuous commands (Enable code of 1). The value is in seconds.
HART Protocol Configuration Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O This parameter specifies the HART function to be executed. Any HART function can be executed, even device specific ones, but only supported commands will return formatted data and classified in floating point data and integer data. 3.3.10 Int. DB Address 0 to 3999 This field specifies the internal database register where the integer or packed ASCII string values returned by the command will be placed.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O HART Protocol Configuration Driver Manual 3.3.14 Enable DB Address 0 to 3999 This field specifies the internal database register to be used to enable the execution of a command. This parameter is only used if "Enable" is "4" or "5". If the value of this database register is "-1", then the command will be executed, otherwise it will not. If the "Enable" value is "5", then after the successful execution of the command this value will become "0" 3.
HART Protocol Configuration Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 3.3.19 Fixed Data Up to 250 HEX values separated by space This parameter is a string of HEX values to be sent with the HART command. There should be at least the number of bytes specified in the "Byte Count" parameter. The bytes should be written in hexadecimal format and separated by a space.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 3.4 HART Protocol Configuration Driver Manual Using the CommonNet Data Map The Data Map section allows you to copy data between areas in the module's internal database. You can copy a maximum of 100 registers per Data Map command, and you can configure a maximum of 200 separate copy commands. You can copy data from the error or status tables in upper memory to internal database registers in the User Data memory area.
HART Protocol Configuration Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 3.4.1 Internal Database Re-mapping Depending on the application, you may need to copy data from one section of the module’s internal database to another section. The [Data Map] section of the CFG file allows a user to selectively copy data registers, one register up to 100 registers at a time, from one internal database to another.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O HART Protocol Configuration Driver Manual 3.4.6 Delay Preset This parameter sets an interval for each Data Map copy operation. The value you put for the Delay Preset is not a fixed amount of time. It is the number of firmware scans that must transpire between copy operations.
HART Protocol Configuration Driver Manual 3.5 ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Downloading a File from PC to the Module 2 3 Use a null-modem serial cable to connected the serial COM port on your PC and the Debug/Configuration serial port on the module. Open the PROJECT menu, and then choose MODULE. On the MODULE menu, choose DOWNLOAD. Wait while ProSoft Configuration scans for communication ports on your PC. When the scan is complete, the Download dialog box opens.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 4 Reference Driver Manual Reference In This Chapter HART Universal Commands ................................................................. 42 HART Common Practice Commands .................................................... 55 Error/Status Data ................................................................................... 85 ProLinx 5108 / 5208 HART Field Connections ......................................
Reference Driver Manual 4.1 ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O HART Universal Commands COMMAND 00 - Read Unique Identifier Description This command gets the long address of the HART device plus other manufacturer information like Manufacturer ID, Device Type Code, Software Revision, Hardware Revision, and so on.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 01 - Read Primary Variable Description This command gets the device Primary Variable and the Primary Variable Units Write Parameters NONE Floating Point Data Returned Word High Byte 0 Primary Variable Value Low Byte 1 Integer Data Returned Word High Byte 0 STATUS WORD 1 Primary Variable Units Code ProSoft Technology, Inc.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 02 - Read Current And Percent Of Range Description This command gets the current of the loop that is forced by the HART device and the Percent of Range of the Current. Write Parameters NONE Floating Point Data Returned Word High Byte 0 Current (mA) Low Byte 1 2 Percent of Range 3 Integer Data Returned Word High Byte 0 STATUS WORD Page 44 of 104 Low Byte ProSoft Technology, Inc.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 03 - Read Dynamic Variables Description This command gets the current and four (predefined) dynamic Variables.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 06 - Write Polling Address Description This command sets the polling address of a HART device. Extreme care should be taken when you use this command because you can loose the communication with the device.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 12 - Read Message Description This command reads an ASCII message contained in the HART Device and written by the Write Message command 17. Write Parameters NONE Floating Point Data Returned NONE Integer Data Returned Word High Byte 0 STATUS WORD 1 Message ASCII Character 0 Message ASCII Character 1 2 Message ASCII Character 2 Message ASCII Character 3 . . . . . .
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 13 - Read Tag, Descriptor and Date Description This command reads an ASCII Tag which identifies the device, an ASCII descriptor of the device and the last Date it has been configured.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 14 - Read PV Sensor Info Description This command gets information about the Primary Variable sensor, like limits and span.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 15 - Read Output Information Description This command gets information about the Primary Variable Output Information.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 16 - Read Final Assembly Number Description This command reads the final assembly number of the HART device. Write Parameters NONE Floating Point Data Returned NONE Integer Data Returned Word High Byte 0 STATUS WORD 1 Final Assembly Number 0 Final Assembly Number 1 2 Final Assembly Number 2 0 ProSoft Technology, Inc.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 17 - Write Message Description This command writes an ASCII message contained in the HART Device and that can be read with command 12. Write Parameters Word High Byte Low Byte 0 Packed ASCII Message Byte 0 Packed ASCII Message Byte 1 1 Packed ASCII Message Byte 2 Packed ASCII Message Byte 3 . . . . . .
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 18 - Write Tag, Descriptor and Date Description This command writes an ASCII Tag which identifies the device, an ASCII descriptor of the device and the last Date it has been configured.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 19 - Write Final Assembly Number Description This command writes the final assembly number of the HART device.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 4.2 Reference Driver Manual HART Common Practice Commands COMMAND 33 - Read Transmitter Variables Description This command gets four user selected dynamic Variables.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 34 - Write Damping Value Description This command writes the damping value of a HART device. Write Parameters Word High Byte 0 Floating Point Damping Value (Sec) Low Byte 1 Floating Point Data Returned Word High Byte 0 Floating Point Damping Value (Sec) Low Byte 1 Integer Data Returned Word High Byte 0 STATUS WORD Page 56 of 104 Low Byte ProSoft Technology, Inc.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 35 - Write Range Values Description This command writes the Upper and Lower range of the Primary Variable Write Parameters Word High Byte Low Byte 0 Range Units Code Floating Point Upper Range Value (Byte 0) 1 Floating Point Upper Range Value (Byte 1) Floating Point Upper Range Value (Byte 2) 2 Floating Point Upper Range Value (Byte 3) Floating Point Lower Range Value (Byte 0) 3 Floating Point Lower Ra
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 36 - Set Upper Range Value Description This command is similar in effect to push the SPAN button of the HART device but doing it remotely through the HART network. Write Parameters NONE Floating Point Data Returned NONE Integer Data Returned Word High Byte 0 STATUS WORD Page 58 of 104 Low Byte ProSoft Technology, Inc.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 37 - Set Lower Range Value Description This command is similar in effect to push the ZERO button of the HART device but doing it remotely through the HART network. Write Parameters NONE Floating Point Data Returned NONE Integer Data Returned Word High Byte 0 STATUS WORD ProSoft Technology, Inc.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 38 - Reset Configuration Changed Flag Description This command resets the status bit that indicates that configuration has been changed. Write Parameters NONE Floating Point Data Returned NONE Integer Data Returned Word High Byte 0 STATUS WORD Page 60 of 104 Low Byte ProSoft Technology, Inc.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 39 - EEPROM Control Description This command operates over the EEPROM changing its settings. Write Parameters Word High Byte Low Byte 0 EEPROM Control Code EEPROM Control Code Floating Point Data Returned NONE Integer Data Returned Word High Byte 0 STATUS WORD 1 EEPROM Control Code ProSoft Technology, Inc.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 40 - Enter Exit Fixed Current Mode Description This command writes the damping value of a HART device. Write Parameters Word High Byte 0 Floating Point Current (mA) Low Byte 1 Floating Point Data Returned Word High Byte 0 Floating Point Current (mA) Low Byte 1 Integer Data Returned Word High Byte 0 STATUS WORD Page 62 of 104 Low Byte ProSoft Technology, Inc.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 41 - Perform Transmitter Self Test Description This command starts the HART device Self Test to find if there is any problem with the device hardware. Write Parameters NONE Floating Point Data Returned NONE Integer Data Returned Word High Byte 0 STATUS WORD ProSoft Technology, Inc.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 42 - Perform Master Reset Description This command performs a master reset in the HART device. Write Parameters NONE Floating Point Data Returned NONE Integer Data Returned Word High Byte 0 STATUS WORD Page 64 of 104 Low Byte ProSoft Technology, Inc.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 43 - Set PV Zero Description This command forces the Primary Value to Zero. Write Parameters NONE Floating Point Data Returned NONE Integer Data Returned Word High Byte 0 STATUS WORD ProSoft Technology, Inc.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 44 - Write PV Units Description This command changes the setting of the Primary Variable units. Write Parameters Word High Byte Low Byte 0 Primary Variable Units Code Primary Variable Units Code Floating Point Data Returned NONE Integer Data Returned Word High Byte 0 STATUS WORD 1 Primary Variable Units Code Page 66 of 104 Low Byte 0 ProSoft Technology, Inc.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 45 - Trim DAC Zero Description This command calibrates the device Digital to analog converter zero. This is done by writing the same current value that is measured in the loop.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 46 - Trim DAC Gain Description This command calibrates the device Digital to analog converter gain. This is done by writing the same current value that is measured in the loop.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 47 - Write Transfer Function Description This command changes the setting of the Transfer Function of the HART device. Write Parameters Word High Byte Low Byte 0 Transfer Function Code Transfer Function Code Floating Point Data Returned NONE Integer Data Returned Word High Byte 0 STATUS WORD 1 Transfer Function Code ProSoft Technology, Inc.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 48 - Read Additional Transmitter Status Description This command gets extended information about the status of the Transmitter. This information is specific for each transmitter. Write Parameters NONE Floating Point Data Returned NONE Integer Data Returned Word High Byte 0 STATUS WORD 1 Additional Status (Byte 0) Additional Status (Byte 1) 2 Additional Status (Byte 2) Additional Status (Byte 3) . . . .
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 49 - Write PV Sensor Serial Number Description This command changes the sensor serial number of the Primary Variable.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 50 - Read Dynamic Variable Assignments Description This command gets the actual assignment of the Dynamic Variables returned with command 3.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 51 - Write Dynamic Variable Assignments Description This command sets the assignment of the Dynamic Variables returned with command 3.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 52 - Set Transmitter Variable Zero Description This command forces a selected transmitter variable to zero. Write Parameters Word High Byte Low Byte 0 Transmitter Variable Code Transmitter Variable Code Floating Point Data Returned NONE Integer Data Returned Word High Byte 0 STATUS WORD 1 Primary Variable Units Code Page 74 of 104 Low Byte 0 ProSoft Technology, Inc.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 53 - Write Transmitter Variable Units Description This command changes a selected transmitter variable unit. Write Parameters: Word High Byte Low Byte 0 Transmitter Variable Code Transmitter Variable Units Code Floating Point Data Returned NONE Integer Data Returned Word High Byte 0 STATUS WORD 1 Primary Variable Units Code ProSoft Technology, Inc.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 54 - Read Transmitter Variable Information Description This command gets information about any selected transmitter variable sensor.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 55 - Write Transmitter Variable Damping Value Description This command writes the Damping Value of a user selected transmitter variable.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 56 - Write Transmitter Variable Sensor Serial Number Description This command writes the Serial Number of a user selected transmitter variable.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 57 - Read Unit Tag Descriptor Date Description This command reads an ASCII Tag which identifies the device, an ASCII descriptor of the device and the last Date it has been configured.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 58 - Write Unit Tag Descriptor Date Description This command writes an ASCII Tag which identifies the device, an ASCII descriptor of the device and the last Date it has been configured.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 59 - Write Number Of Response Preambles Description This command sets the number of preambles that the HART slave will use in every command response. Write Parameters Word High Byte Low Byte 0 Number of Response Preambles Number of Response Preambles Floating Point Data Returned NONE Integer Data Returned Word High Byte 0 STATUS WORD 1 Number of Response Preambles ProSoft Technology, Inc.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 108 - Write Burst Mode Command Number Description This command sets the command number that the HART device will use in Burst Mode. Write Parameters Word High Byte Low Byte 0 Burst Mode Command Number Burst Mode Command Number Floating Point Data Returned NONE Integer Data Returned Word High Byte 0 STATUS WORD 1 Burst Mode Command Number Page 82 of 104 Low Byte 0 ProSoft Technology, Inc.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual COMMAND 109 - Burst Mode Control Description This command sets the HART device Burst Mode. Write Parameters Word High Byte Low Byte 0 Burst Mode Control Code Burst Mode Control Code Floating Point Data Returned NONE Integer Data Returned Word High Byte 0 STATUS WORD 1 Burst Mode Control Code Low Byte 0 1 = ON 0 = Off ProSoft Technology, Inc.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O COMMAND 110 - Read All Dynamic Variables Description This command gets all dynamic Variables.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 4.3 Reference Driver Manual Error/Status Data The module error/status data areas are discussed in this section. The module contains three areas related to this data. The user defines the location of these data sets in the virtual database of the module.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Status Register Name Description 10701 Comm State Channel 0 communication state machine value (used for debugging) 0 Startup 1 Idle 2 Transmit Pending 3 Transmit 4 Receive 5 Post Transmit 6 Idle, Waiting 10702 Device Status (bit mapped) Each bit in this word corresponds to a slave address on the network starting at bit 1 for slave address 1. Bit 0 is not used. If the bit is set, the slave is in error.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual HART Command List Error Data Each command in the command list for each HART channel has a word value for a status/error code. This error data list can be read using the Configuration/Debug Port and can be placed in the module’s internal database.
Reference Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Protocol Error Codes These are error codes that are part of the HART protocol.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual Bit 7 of First Byte = 0 Command Error Bit 2 Analog Output Saturated Bit 1 Variable (not Primary) Out Of Limits Bit 0 Primary Variable Out of Limits Command Specific Errors 8 Update Failed Update In Progress Set to Nearest Possible Value 9 Applied Process Too High Lower Range Value Too High Not in Fixed Current Mode 10 Applied Process Too Low Lower Range Value Too Low Multi-drop Not Supported 11 In Multi-drop Mo
Reference Driver Manual 4.4 ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O ProLinx 5108 / 5208 HART Field Connections HART field instruments are divided into four types; A through D, depending on power requirements and whether the device sinks or sources a bias or operating current from the network. The following table defines the categories: Type Description A Type A field instruments sink direct current from the network and receive operating power from the network.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Reference Driver Manual 4.4.3 Wiring Diagrams If field instrument wiring is shielded, terminate shields at the ground terminals of the HART connector TB1. Do not terminate the shields at the instrument. ProSoft Technology, Inc.
Reference Driver Manual Page 92 of 104 ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O ProSoft Technology, Inc.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O ProSoft Technology, Inc.
Reference Driver Manual Page 94 of 104 ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O ProSoft Technology, Inc.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 5 Support, Service & Warranty Driver Manual Support, Service & Warranty In This Chapter Contacting Technical Support ............................................................... 95 Return Material Authorization (RMA) Policies and Conditions............... 97 LIMITED WARRANTY ........................................................................... 99 Contacting Technical Support ProSoft Technology, Inc.
Support, Service & Warranty Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Internet Web Site: www.prosoft-technology.com/support E-mail address: support@prosoft-technology.com Asia Pacific (location in Malaysia) Tel: +603.7724.2080, E-mail: asiapc@prosoft-technology.com Languages spoken include: Chinese, English Asia Pacific (location in China) Tel: +86.21.5187.7337 x888, E-mail: asiapc@prosoft-technology.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 5.1 Support, Service & Warranty Driver Manual Return Material Authorization (RMA) Policies and Conditions The following Return Material Authorization (RMA) Policies and Conditions (collectively, "RMA Policies") apply to any returned product. These RMA Policies are subject to change by ProSoft Technology, Inc., without notice. For warranty information, see Limited Warranty (page 99).
Support, Service & Warranty Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 5.1.3 Returning Units Out of Warranty a) Customer sends unit in for evaluation to location specified by ProSoft Technology, freight prepaid. b) If no defect is found, Customer will be charged the equivalent of $100 USD, plus freight charges, duties and taxes as applicable. A new purchase order will be required.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 5.2 Support, Service & Warranty Driver Manual LIMITED WARRANTY This Limited Warranty ("Warranty") governs all sales of hardware, software, and other products (collectively, "Product") manufactured and/or offered for sale by ProSoft Technology, Incorporated (ProSoft), and all related services provided by ProSoft, including maintenance, repair, warranty exchange, and service programs (collectively, "Services").
Support, Service & Warranty Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 5.2.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Support, Service & Warranty Driver Manual 5.2.
Support, Service & Warranty Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O 5.2.6 Limitation of Remedies ** In no event will ProSoft or its Dealer be liable for any special, incidental or consequential damages based on breach of warranty, breach of contract, negligence, strict tort or any other legal theory.
ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Index [ [Analog HART Card x] • 28 [HART PORT x COMMANDS] • 31 [HART PORT x] • 29 A Agency Approvals and Certifications • 4 Allocation of Risks • 102 Auto-Poll Code • 30 Auto-Poll DB Address • 30 Auto-Poll Disabled Mode • 24 Auto-Poll Swap Float • 30 Auto-Polling • 21 B Burst Mode • 21 Byte Count • 35 C CHx High • 28 CHx Low • 28 COMMAND 00 - Read Unique Identifier • 42 COMMAND 01 - Read Primary Variable • 43 COMMAND 02 - Read Current And Percent
Index Driver Manual ProLinx-HART ♦ ProLinx Gateway HART Master with Analog I/O Enabled • 29 Error/Status Data • 85 F Fixed Data • 36 Float DB Address • 33 FP Word Count • 33 From Address • 38 Function Code • 33 Functional Overview • 15 Functional Specifications - HART Analog • 17 H HART Channel 0 Status Data Map • 85 HART Channel Driver Access to Database • 20 HART Channels • 16 HART Command Entry Formats • 32 HART Command List • 21 HART Command List Error Data • 87 HART Common Practice Commands • 31, 5