OBJECT REQUEST RESPONSE
Obj Var Description Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
NOTES
3 Short Floating
Point Analog
Output Block
3, 4, 5,
6
17, 28 129 Echo of
Request
40 Slave will respond to this request
4 Long Floating
Point Analog
Output Block
3, 4, 5,
6
17, 28 129 Echo of
Request
72 Slave will respond to this request
50 0 Time and Date:
All Variations
2 07, With
Quant=1
48 Slave will use variation 1
1 Time and Date 2 07, With
Quant=1
48 Slave will respond to this variation
2 Time and Date
With Interval
80 Slave will return Unknown Object to
this request
51 0 Time and Date
CTO: All
Variations
Slave will return Unknown Object to
this request
1 Time and Date
CTO
129,
130
07, With
Quant=1
48 Slave will return Unknown Object to
this request
2 Unsynchronized
Time and Date
CTO
129,
130
07, With
Quant=1
48 Slave will return Unknown Object to
this request
52 0 Time Delay: All
Variations
1 Time Delay
Coarse
129 07, With
Quant=1
16 Slave will never return this variation
2 Time Delay
Fine
129 07, With
Quant=1
16 Slave will return this variation to
functions 0D, 0E, and 17
60 0 Not Defined
Not Defined in DNP
1 Class 0 Data 1 06
Slave will respond to this variation
with all static data
2 Class 1 Data 1 06, 07,
08
Slave will respond to this variation
(No class 1 data defined in
application)
3 Class 2 Data 1 06, 07,
08
Slave will respond to this variation
with all class 2 data (binary input
events)
4 Class 3 Data 1 06, 07,
08
Slave will respond to this variation
with all class 3 data (analog input
events)
70 0 Not Defined
Not Defined in DNP
1 File Identifier
Slave will return Unknown Object to
this request
80 0 Not Defined
Not Defined in DNP
1 Internal
Indications
2 00,
Index=7
24 Slave will respond to this variation
81 0 Not Defined
Not Defined in DNP