DEVICE PROFILE DOCUMENT
When reporting Event Data as a slave unit
Time-outs while waiting for:
Data Link Confirm : Configurable at module start-up (1 to 65535 mSec)
Complete Application Fragment : Configurable at module start-up
Application Confirm : Configurable at module start-up (1 to 65535 mSec)
Complete Application Response : None
Sends/Executes Control Operations:
WRITE Binary Outputs : Never
SELECT/OPERATE : Always
DIRECT OPERATE : Always
DIRECT OPERATE-NO ACK : Always
Count > 1 : Always (1 to 255)
Pulse On : Always
Pulse Off : Always
Latch On : Always
Latch Off : Always
Queue : Never
Clear Queue : Never
Reports Binary Input Change Events when no specific
variation requested:
Reports time-tagged Binary Input Change Events when no
specific variation requested:
Only time-tagged
Binary Input Change with Time
Sends Unsolicited Responses: Sends Static Data in Unsolicited Responses:
This is configurable at module start-up. If the number of
events for the Binary or Analog Input Events is greater than
0, unsolicited responses are supported. Use the
Enable/Disable Unsolicited function code from the DNP
master for control.
Never
Default Counter Object/Variation: Counters Roll Over at:
Object : 20
32 Bits
Variation : 5
Sends Multi-Fragment Responses: Yes