User manual

Reference ProLinx DNPS ProLinx Gateway
User Manual DNP 3.0 Slave
ProSoft Technology, Inc. Page 69 of 86
December 1, 2009
DNP V3.00
DEVICE PROFILE DOCUMENT
When reporting Event Data as a slave unit
Time-outs while waiting for:
Data Link Confirm : Configurable at module start-up (1 to 65535 mSec)
Complete Application Fragment : Configurable at module start-up
Application Confirm : Configurable at module start-up (1 to 65535 mSec)
Complete Application Response : None
Sends/Executes Control Operations:
WRITE Binary Outputs : Never
SELECT/OPERATE : Always
DIRECT OPERATE : Always
DIRECT OPERATE-NO ACK : Always
Count > 1 : Always (1 to 255)
Pulse On : Always
Pulse Off : Always
Latch On : Always
Latch Off : Always
Queue : Never
Clear Queue : Never
Reports Binary Input Change Events when no specific
variation requested:
Reports time-tagged Binary Input Change Events when no
specific variation requested:
Only time-tagged
Binary Input Change with Time
Sends Unsolicited Responses: Sends Static Data in Unsolicited Responses:
This is configurable at module start-up. If the number of
events for the Binary or Analog Input Events is greater than
0, unsolicited responses are supported. Use the
Enable/Disable Unsolicited function code from the DNP
master for control.
Never
Default Counter Object/Variation: Counters Roll Over at:
Object : 20
32 Bits
Variation : 5
Sends Multi-Fragment Responses: Yes