User manual
Reference ProLinx DNPS ♦ ProLinx Gateway
User Manual DNP 3.0 Slave
ProSoft Technology, Inc. Page 41 of 86
December 1, 2009
3 Reference
In This Chapter
Product Specifications...........................................................................41
Communication Port Cables..................................................................44
Functional Overview..............................................................................50
DNP Collision Avoidance.......................................................................64
IIN Response: Slave Port ......................................................................65
IIN Bit Definitions...................................................................................66
Event Size Computation........................................................................67
Device Profile ........................................................................................68
Subset Definition ...................................................................................70
3.1 Product Specifications
3.1.1 DNP 3.0 Slave Port Specifications
Type Specifications
General Parameters
Internal Database Binary Inputs: 0 to 100 word count
Analog Inputs: 0 to 100 points of analog input data
Float Inputs: 250 points
Double Inputs: 125 points
Counters: 0 to 50 points of counter data
Binary Outputs: 0 to 100 word count
Analog Outputs: 0 to 100 points of analog output
Float Outputs: 250 points
Double Outputs: 125 points
Binary Input Events: 0 to 100 binary input event buffer
Analog Input Events: 0 to 100 analog input event buffer
Communication parameters Port 0: Baud Rate: 110 to 38.4K baud
Stop Bits: 1
Data Size: 8 bits
Parity: None
RTS Timing delays: 0 to 65535 milliseconds
DNP Mode DNP 3.0 Slave - Level 2
DNP Object Support
See Reference chapter for full Object Definition document