User manual
ILX34-AENWG ♦ Point I/O Platform Diagnostics and Troubleshooting
Wireless POINT I/O Adapter User Manual
ProSoftTechnology,Inc. Page85of209
September19,2011
Field Description
ConnTimeouts Timeoutsoccurwhenthecontrollerdoesnotreceivepacketsfroman
I/OconnectionwithintheRPIrequirements.Thetimeoutoccurs
within4xRPIvalue.
IfthecontrollerhasnotheardfromtheI/Oin4RPItimes,ittimes
out.
Theminimumtimeoutvalueis100ms.Therefore,even
iftheRPIis
4ms,atimeoutwillnotoccuruntilnopacketshavebeenheardfrom
theI/Oinover100ms.
Ifthenumberoftimeoutsishigh,thenetworktrafficislikelytoohigh.
LED Status:
Field Description
ModuleStatus Flashingred=anerrorcondition
Solidgreen=functioningproperly
NetworkActivity Rapidlyflashinggreen=successfuldatatransferactivity
Slowlyflashinggreen=anissueordifficultywithinthenetwork
Flashingred=anerrorcondition
NetworkStatus Flashinggreen=anerrorcondition
Solidgreen=functioningproperly
PointBusStatus Flashingred=anerrorcondition
Solidgreen=functioningproperly
Module Settings
Field Description
ChassisSize Displaysthechassissizethatisstoredintheadapter.(page63)
Switches Displaystheconfigurationofthethumbwheelswitchesonthefaceof
theILX34‐AENWGadapter(page25)