ILX34-AENWG Point I/O Platform About the Example Applications
Wireless POINT I/O Adapter User Manual
ProSoftTechnology,Inc. Page63of209
September19,2011
3.4.4 Verify the Chassis Size
YoumustconfigurethechassissizefortheILX34AENWGbeforeyoucanmakeanyI/O
connections(page43).Thedefaultsettingforthechassissizeis1slot,whichrepresentsthe
adapterbyitself.
Whentheadapter'snonvolatilechassissizedoesnotmatchtheactualnumberofmodules
present
onitsbackplane,theadapterdoesnotmakeanyI/Oconnectionsandanerroroccurs,as
shownintheM
ODULEPROPERTIESdialogbox.
ThisproceduresynchronizesthechassissizevaluefromtheRSLogix5000softwareintothe
ILX34AENWGhardware.Youmustbeonlinetoperformthisprocedure.
1 VerifythatRSLogix5000softwareisonlinetotheprocessor.
2 DoubleclicktheILX34AENWG
adapterunderI/OCONFIGURATIONintheCONTROLLER
ORGANIZATIONwindow.ThisactionopenstheMODULEPROPERTIESdialogbox.
3 OntheM
ODULEPROPERTIESdialogbox,clicktheCONNECTIONtab.NoticethattheMODULEFAULT
areaofthedialogboxcontainsinformationabouttheerrorcode.