User manual

ILX34-AENWG Point I/O Platform Configure the ILX34-AENWG
Wireless POINT I/O Adapter User Manual
ProSoftTechnology,Inc. Page47of209
September19,2011
5 Clickthevalue2andchangeitto0,whichchangesthevoltagerangeto‐10to+10Vdcfor
channel0.
Notethefollowing:
o Thecontrollersendstheconfigurationdataonlywhenitfirstestablishestheconnection.
o Afteryoumodifyanyofthetagvalues,youmustdownloadtheupdatedinformation
intothemodule.
ThebestwaytodothisistoenterthecorrectcodenumberintheRangeTypefieldwhen
youaddtheI/OtotheI/OConfigurationtree.Youthendownloadlater.
Ifyou
needtochangeanyofthemodule'sconfigurationparametersafteraddingthe
module,clicktheC
ONNECTIONtabandinhibitthemodule,applythechanges,andthen
uninhibitthemodule.Thisactionbreakstheconnectionandcausestheconfiguration
informationtobedownloadedrightaftertheconnectionismade.
Important: Switching the controller from Program to Run mode does not change the module
connection status and does not re-send module configuration data. We highly recommend that you
use the inhibit/uninhibit process and avoid power cycling.
6 RightclicktheILX34AENWGadapterandselectP
ROPERTIES.
7 ClicktheC
ONNECTIONtab.NoticethattheStatusmessageatthebottomleftcornerofthe
dialogboxreads"F
AULTED".
Themoduleisfaultedbecause,eventhoughyousetuptheadapter'sPOINTI/Ochassissize
totheactualnumberofmodules,plustheadapter,theadapterstillremembersthesizeof1
(thefactorydefaultvalue)untilyouresetthissizemanually.
Note: You must be online to the adapter to change this setting.