User manual
ILX34-AENWG ♦ Point I/O Platform Configure the ILX34-AENWG
Wireless POINT I/O Adapter User Manual
ProSoftTechnology,Inc. Page45of209
September19,2011
2.5 Configure 1734 POINT I/O Modules
ThepreferredmethodtoconfigurePOINTI/OmodulesistousetheM ODULEPROPERTIESdialogbox
foreachPOINTI/Omodule,asdescribedintheUserManualforthemodule.Thefollowingsteps
showyouhowtoconfigurethemodulebyeditingtheControllerTags.
1 IntheC
ONTROLLERORGANIZATIONwindow,double‐clickCONTROLLERTAGS,andthenclickthe
M
ONITORTAGStab,atthebottomleftcorneroftheControllerTagsdialogbox.
LookatthebottomofthescreentomakesureyouareintheMonitorTagstab.
Inthisexample,youwillconfigureananaloginputmodule1734‐IE2V,installedinslot1.You
willconfigureChannel0of
thismoduletooperateovertherange‐10to+10Vdc.
2 ExpandtheconfigurationtagILX34_AENWG:2:C.
Fromhere,youcansetthemodule'sconfigurationandalarms.Enterthevaluesthatwould
correspondtothedesiredrange.Therangetypedefaultvaluefora1734‐IE2Vmoduleis2,
whichisequalto0to10Vdc.
3 Expandtheconfigurationtagfor
themoduleinslot4,ILX34_AENWG:2:CH0RANGETYPE.