User manual

ILX34-AENWG Point I/O Platform Configure the ILX34-AENWG
Wireless POINT I/O Adapter User Manual
ProSoftTechnology,Inc. Page43of209
September19,2011
2.3.1 Configure Chassis Size
TheILX34AENWGrequiresconfiguration ofitschassissizebeforeyoucanmakeanyI/O
connections.Thedefaultsettingforthechassissizeis1slot,whichrepresentstheadapterby
itself,andallowsfornoI/O.
Youmustsetthechassissizetoanumberequaling1slotforthe
adapterplus1slotforeachI/O
modulepresentintheadapter'sbackplane.Forexample,theadapterplus2I/Omodulesusesa
chassissizeof3.Theadapterstoresthischassissizesettinginnonvolatilestorage.
Whentheadapter'snonvolatilechassissizedoesnotmatchtheactual
numberofmodules
presentonitsbackplane,theadapterdoesnotmakeanyI/Oconnectionsandanerroroccurs.
1 IntheModuleDefinitionareaoftheGeneraltab,clicktheC
HANGEbutton.Thisactionopens
theM
ODULEDEFINITIONdialogbox.
2 SelecttheChassisSizeforyourprojectfromthedropdownlist,andthenClickOK
toclose
theM
ODULEDEFINITIONdialogbox.Inalaterstep,youwillverifythechassissizewhenyouare
onlinewiththeILX34AENWG(page45).