Program Fault Note
ProgrammingFaultErrorbit‐Ifanincomplete,incorrect,orconflictingsetofconfiguration
parametersissenttothemodule,theProgramFaultbitisasserted,andanerrorcodeplacedin
theProgrammingErrorCodeword(assembly6816).Themodulewillnotenteranormal
operationalstate.Bitdefinitions(decimal)for
theerrorcodesare:
Error Bit Description
10 An invalid assembly was chosen for poll consumption (0, 105, or 106 are valid).
9 The decimal point position is outside of the acceptable range.
8 Counter 0 window ON & OFF values are equal and not zero OR
Counter 0 window ON & OFF value is greater than the Rollover.
7 A tie has been connected to an unprogrammed window.
6 A configuration was selected that requires the scalar and none was programmed OR
Multiple scalars were selected.
5 The preset is out of range (Rollover).
4 A rollover of zero was programmed through PWM was not selected OR
A rollover was programmed and PWM was selected OR
Rollover is out of range (>0x01000000).
3 A configuration requiring a time base was selected and no gate interval was set OR
Gate interval is out of range (>200) OR
Product of time base and gate interval is greater than 3 seconds.
2 A time base was entered that is not a multiple of 10 OR
Time base is out of range (>3000, or 3 seconds).
1 ZF/BF/AF were selected and no filter was programmed OR
Multiple filters were selected.
0 A reserved configuration/mode was programmed.