1734 POINT I/O Catalog Number RSLogix5000 Module Description
1734-IJ 1 Channel 5V dc Encoder / Counter
1734-IK 1 Channel 15…24V dc Encoder / Counter
Input Data Data Type Default Value Valid Data Values
Present Data DINT 0 0…16,777,215
Stored Data DINT 0 -2,147,483,648…
2,147,483,647
(0…4,294,967,295)
Status INT 0
Zero Frequency Detected BIT 1
0=No Fault
1=Fault Detected
Stored Data Count_2 BIT 2
Cycles through 0, 1, 2, 3, 0,
Stored Data Count_3 BIT 3
Increments after update
A Input Status
B Input Status
Z Input Status
BIT 4
BIT 5
BIT 6
0=Input A/B/Z is Off
1=Input A/B/Z is On
Not Ready BIT 13
0=Module Ready
1=Module Initializing
EEPROM Fault BIT 14
0=No Fault
1=EEPROM data bad
Program Fault
(incomplete / incorrect / conflict)
BIT 15
0=No Fault
1=Bad Configuration
(See Program Fault Note)
Stored Data
Tointerpretvaluesfrom‐2,147,483,648to‐1,usethisconversionformula:
StoredDataTagValue+4,294,967,296=ActualStoredDataTagValue.
Example:forareadvalueof‐1,794,967,296:1,794,967,296+4,294,967,296=2,500,000,000
actualvalue