User manual

Ladder Logic ILX34-AENWG Point I/O Platform
User Manual Wireless POINT I/O Adapter
Page160of209 ProSoftTechnology,Inc.
September19,2011
1734-VHSC24, 1734-VHSC5
1734 POINT I/O Catalog Number RSLogix5000 Module Description
1734-VHSC24 1 Channel 15…24V dc Very High-speed Counter
1734-VHSC5 1 Channel 5V dc Very High-speed Counter
Input Data Data Type Default Value Valid Data Values
Present Data DINT 0 0…16,777,215
Stored Data DINT 0 -2,147,483,648…2,147,483,647
(0…4,294,967,295)
Status INT 0
Zero Frequency Detected BIT 1
0=No Fault
1=Fault Detected
Stored Data Count_2
Stored Data Count_3
BIT 2
BIT 3
Cycles through 0, 1, 2, 3, 0,
Increments after update
A Input Status
B Input Status
Z Input Status
BIT 4
BIT 5
BIT 6
0=Input A/B/Z is Off
1=Input A/B/Z is On
Output Status_8 (Output 0)
Output Status_9 (Output 1)
BIT 8
BIT 9
0=Output is Off
1=Output is On
Output Fault_10 (Output 0)
Output Fault_11 (Output 1)
BIT 10
BIT 11
0=No Fault
1=Open or Over Load
Not Ready BIT 13
0=Module Ready
1=Module Initializing
EEPROM Fault BIT 14
0=No Fault
1=EEPROM data bad
Program Fault
(incomplete / incorrect / conflict)
BIT 15
0=No Fault
1=Bad Configuration
(See Program Fault Note)
Stored Data
Tointerpretvaluesfrom‐2,147,483,648to‐1,usethisconversionformula:
StoredDataTagValue+4,294,967,296=ActualStoredDataTagValue.
Example:forareadvalueof‐1,794,967,296:
1,794,967,296+4,294,967,296=2,500,000,000actualvalue