1734-OE2C
1734 POINT I/O Catalog Number RSLogix5000 Module Description
1734-OE2C 2 Channel Analog Current Output
Configuration Data Data Type Default Value Valid Data Values
Idle Mode Channel 1 SINT 1 0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value
Limit Alarm Latch Channel 1 SINT 0 0=No Latching
1=Alarms Latch
Alarm Disable Channel 1 SINT 0 0=Alarms Enabled
1=Alarms Disabled
Input Data Data Type Default Value Valid Data Values
Status Byte Channel 0 SINT 0 Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Status Byte Channel 1 SINT 0 Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Output Data Data Type Default Value Valid Data Values
Data Channel 0 INT 0 -32,768…32,767
Data Channel 1 INT 0 -32,768…32,767