September19,2011
1734-IT2
1734 POINT I/O Catalog Number RSLogix5000 Module Description
1734-IT2 2 Channel Thermocouple Input, Isol.
Configuration Data Data Type Default Value Valid Data Values
Temperature Mode Channel 1 SINT 1 0=mV/Custom Scale
1=°C
2=°F
3=°K
4=°R
Cold Junction Enable Channel 1 SINT 1 0=Disabled
1=Enabled
Cold Junction Offset Channel 1 INT 0 0…7,000 (0.00…70.00)
Input Data Data Type Default Value Valid Data Values
Data Channel 0 INT 0 -32,768…32,767
Data Channel 1 INT 0 -32,768…32,767
Status Byte Channel 0 SINT 0 Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange
Status Byte Channel 1 SINT 0 Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange
Cold Junction Data INT 0 -32,768…32,767
Output Data Data Type Default Value Valid Data Values
None
