User manual
Ladder Logic ILX34-AENWG ♦ Point I/O Platform
User Manual Wireless POINT I/O Adapter
Page146of209 ProSoftTechnology,Inc.
September19,2011
1734-IE2V
1734 POINT I/O Catalog Number RSLogix5000 Module Description
1734-IE2V 2 Channel Analog Voltage Input
Input Data Data Type Default Value Valid Data Values
Data Channel 0 INT 0 -32,768…32,767
Data Channel 1 INT 0 -32,768…32,767
Status Byte Channel 0 SINT 0 Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange
Status Byte Channel 1 SINT 0 Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange
Output Data Data Type Default Value Valid Data Values
None