5.2.9 Digital 4 POINT Output - With Over Load Diagnostic Status
1734 POINT I/O Catalog Number RSLogix5000 Module Description
1734-OV4E 4 POINT 10V…28V dc Electronically Fused Output, Sink
Configuration Data Data Type Default Value Valid Data Values
Fault Mode - POINT 0, 1, 2, 3 SINT, BIT 0 0=Fault Value
1=Hold Last State
Fault Value - POINT 0, 1, 2, 3 SINT, BIT 0 0=Off
1=On
Program Mode - POINT 0, 1, 2, 3 SINT, BIT 0 0=Program Value
1=Hold Last State
Program Value - POINT 0, 1, 2, 3 SINT, BIT 0 0=Off
1=On
Auto Restart Enable - POINT 0, 1, 2, 3
(Over Load Behavior)
SINT, BIT 0 0=Latch Off
1=Auto Retry
Fault Latch Enable - POINT 0, 1, 2, 3
(Over Load)
SINT, BIT 0 0=No Latching
1=Alarms Latch
Input Data Data Type Default Value Valid Data Values
Status Data - POINT 0, 1, 2, 3
(Over Load)
SINT, BIT 0 0=Off
1=On (Load Fault)
Output Data Data Type Default Value Valid Data Values
Output Data - POINT 0, 1, 2, 3 SINT, BIT 0 0=Off
1=On