September19,2011
5.2.3 Digital 2 POINT Input
1734 POINT I/O Catalog Number RSLogix5000 Module Description
1734-IA2 2 POINT 120V ac Input
1734-IB2 2 POINT 10V…28V dc Input, Sink
1734-IM2 2 POINT 240V ac Input
1734-IV2 2 POINT 10V…28V dc Input, Source
Configuration Data Data Type Default Value Valid Data Values
Filter Off On Time - POINT 0 INT 1,000
-32,768…32,767 s (see note)
(0…65,535)
Filter On Off Time - POINT 0 INT 1,000
-32,768…32,767 s (see note)
(0…65,535)
Filter Off On Time - POINT 1 INT 1,000
-32,768…32,767 s(see note)
(0…65,535)
Filter On Off Time - POINT 1 INT 1,000
-32,768…32,767 s(see note)
(0…65,535)
Input Data Data Type Default Value Valid Data Values
Input Data - POINT 0, 1 SINT, BIT 0 0=Off
1=On
Output Data Data Type Default Value Valid Data Values
None
Note: POINT I/O Modules support the Unsigned Integer data type UINT (0 to 65,535 range).
RSLogix 5000 software supports the signed Integer data type INT (-32,768 to +32,767 range).
To enter Filter values from +32,768 to +65,535 s, use this conversion formula:
Desired Filter Value (in s) - 65536 = Entered Filter Value (in s).
Example: for a 40 ms filter time, 40000 - 65536 = -25536