User manual

About the Example Applications ILX34-AENWG Point I/O Platform
User Manual Wireless POINT I/O Adapter
Page 68 of 177 ProSoft Technology, Inc.
August 16, 2013
When the adapter's non-volatile chassis size does not match the actual number
of modules present on its backplane, the adapter does not make any I/O
connections and an error occurs, as shown in the MODULE PROPERTIES dialog
box.
This procedure synchronizes the chassis size value from the RSLogix 5000
software into the ILX34-AENWG hardware. You must be online to perform this
procedure.
1 Verify that RSLogix 5000 software is online to the processor.
2 Double-click the ILX34-AENWG adapter under I/O CONFIGURATION in the
CONTROLLER ORGANIZATION window. This action opens the MODULE
PROPERTIES dialog box.
3 On the MODULE PROPERTIES dialog box, click the CONNECTION tab. Notice
that the MODULE FAULT area of the dialog box contains information about the
error code.