ProSoft Technology, Inc. Page 65 of 177
August 16, 2013
4 Click the CONNECTION tab, and then change the RPI value for the module
from 20 (the default) to 10 (the recommended value for digital modules). This
value determines how often to exchange data with the ILX34-AENWG
adapter.
5 Click OK save the configuration.
The following illustration shows the I/O Configuration for this project.
3.5.3 Edit the Controller Tags
When you add modules to the I/O configuration, the system creates tags for
those modules to use in the application program.
For the example application, you need to add one more controller tag.
1 Double-click the CONTROLLER TAGS folder in the project dialog.
The action opens the CONTROLLER TAGS dialog box. You will see the tags
created for the ILX34-AENWG adapter and digital I/O modules.