About the Example Applications ILX34-AENWG ♦ Point I/O Platform
User Manual Wireless POINT I/O Adapter
Page 54 of 177 ProSoft Technology, Inc.
August 16, 2013
b) Slot
In the MODULE DEFINITION area of the dialog box, notice that the default
Connection type is RACK OPTIMIZATION.
4 Click the CONNECTION tab, and then change the RPI value for the module
from 20 (the default) to 10 (the recommended value for digital modules). This
value determines how often to exchange data with the ILX34-AENWG
adapter.
Important: To avoid overloading the ILX34-AENWG adapter, we recommend that RPI be no less
than 10 ms for rack connections and 50 ms for direct connections.
5 Click OK save the configuration.