About the Example Applications ILX34-AENWG Point I/O Platform
User Manual Wireless POINT I/O Adapter
Page 52 of 177 ProSoft Technology, Inc.
August 16, 2013
4 Click the CONNECTION tab, and then change the RPI value for the module
from 20 (the default) to 50 (the recommended value for analog or specialty
modules). This value determines how often to exchange data with the ILX34-
AENWG adapter.
Important: To avoid overloading the ILX34-AENWG adapter, we recommend that RPI be no less
than 10 ms for rack connections and 50 ms for direct connections.
5 Click OK save the configuration.
The following illustration shows the I/O Configuration for this project.
3.4.2 Add the Digital Output Module and Configure for Rack
Optimization
1 Right-click the ILX34-AENWG adapter under the I/O Configuration folder and
select NEW MODULE.