User manual

ILX34-AENWG Point I/O Platform Configure the ILX34-AENWG
Wireless POINT I/O Adapter User Manual
ProSoft Technology, Inc. Page 43 of 177
August 16, 2013
7 Click the CONNECTION tab. Notice that the Status message at the bottom left
corner of the dialog box reads "FAULTED".
The module is faulted because, even though you set up the adapter's POINT
I/O chassis size to the actual number of modules, plus the adapter, the
adapter still remembers the size of 1 (the factory default value) until you reset
this size manually.
Note: You must be online to the adapter to change this setting.
8 Click the CHASSIS SIZE tab.