User manual
Configure the ILX34-AENWG ILX34-AENWG ♦ Point I/O Platform
User Manual Wireless POINT I/O Adapter
Page 40 of 177 ProSoft Technology, Inc.
August 16, 2013
1 In the Module Definition area of the General tab, click the CHANGE button.
This action opens the MODULE DEFINITION dialog box.
2 Select the Chassis Size for your project from the dropdown list, and then
Click OK to close the MODULE DEFINITION dialog box. In a later step, you will
verify the chassis size when you are online with the Configure 1734 POINT
I/O Modules (page 40).
2.4 Add POINT Modules Under the Adapter
1 Right-click the ILX34-AENWG adapter under I/O configuration to add a new
module.
Your second module is in slot 1.
2 Select the module from the MODULE TYPE list, and click OK.
3 In the MODULE PROPERTIES dialog, enter the following information:
a) Name
b) Slot
4 Click the CONNECTION tab, and set the RPI:
o For digital modules, enter 10 ms
o For analog or specialty modules, enter 50 ms.
5 Click FINISH.
Repeat these steps to add all of the POINT I/O modules connected to the
ILX34-AENWG adapter.
2.5 Configure 1734 POINT I/O Modules
The preferred method to configure POINT I/O modules is to use the MODULE
PROPERTIES dialog box for each POINT I/O module, as described in the User
Manual for the module. The following steps show you how to configure the
module by editing the Controller Tags.
1 In the CONTROLLER ORGANIZATION window, double-click CONTROLLER TAGS,
and then click the MONITOR TAGS tab, at the bottom left corner of the
Controller Tags dialog box.