User manual

ILX34-AENWG Point I/O Platform Ladder Logic
Wireless POINT I/O Adapter User Manual
ProSoft Technology, Inc. Page 129 of 177
August 16, 2013
1734-IR2
1734 POINT I/O Catalog Number
RSLogix5000 Module Description
1734-IR2
2 Channel RTD Input
Configuration Data
Data Type
Default Value
Valid Data Values
Sensor Type Channel 1
SINT
1
0=Ohms
385
2=200 Pt 385
5=100 JPt 3916
6=200 JPt 3916
9=10 Cu 427
10=120 Ni 672
11=100 Ni 618
12=120 Ni 618
Temperature Mode Channel 1
SINT
1
0=Custom Scale
1=°C
2=°F
3=°K
4=°R
Notch Filter (Channel 0 & 1)
SINT
1
0=50 Hz
1=60 Hz
2=100 Hz
3=120 Hz
4=200 Hz
5=240 Hz
6=300 Hz
7=400 Hz
8=480 Hz
Input Data
Data Type
Default Value
Valid Data Values
Data Channel 0
INT
0
-32,768…32,767
Data Channel 1
INT
0
-32,768…32,767
Status Byte Channel 0
SINT
0
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange