Ladder Logic ILX34-AENWG ♦ Point I/O Platform
User Manual Wireless POINT I/O Adapter
Page 118 of 177 ProSoft Technology, Inc.
August 16, 2013
2 In the edit window, change the value of the READDATA array from INT[600] to
INT[1000] as shown, and then click APPLY.
Note: If RSLogix resets your data values, refer to the backup copy of your program to re-enter your
configuration parameters.
3 Next, navigate to CONTROLLER TAGS and double click to open an edit
window. Click the MONITOR TAGS tab at the bottom of the edit window.
4 Click [+] to expand the AENWG.CONFIG.MODDEF section, and then change
the READREGCNT parameter from 600 to 1000.
5 Save and download the sample program to the processor.
6 Go Online with the ControlLogix processor, and then toggle the
AENWG.CONTROL.WARMBOOT bit to download the configuration to the
ILX34-AENWG module.
Note: Any changes made to the AENWG.CONFIG or WriteData arrays must be downloaded to the
ILX34-AENWG module. The use of the AENWG.CONTROL.WarmBoot or
AENWG.CONTROL.ColdBoot bit will cause the ILX34-AENWG module to re- read the
configuration from the ControlLogix processor.
To modify the WRITEDATA array, follow the steps in this topic, but substitute
WRITEDATA for ReadData throughout. Also, make sure that the READDATA and
WRITEDATA arrays do not overlap in the module memory. For example, if your
application requires 2000 words of WriteData starting at register 0, then your
AENWG.CONFIG.MODDEF.READSTARTREG must be set to a value of 2000 or
greater.
5.2 1734 POINT I/O Module/RSLogix 5000 Controller Tag Reference
Attention: You must use series C POINT I/O modules with the ILX34-AENWG adapter. Series A
or B POINT I/O modules will not work with this adapter.