PSTSL Installation Manual

WARNING
Important Safety Information
2
3 4
1
Installing Your New Thermostat
Replacing Existing Thermostat
WARNING!
Read BEFORE Testing
Default Thermostat Settings
Setting Second Stage Differential
Setting Temperature Differentials
5 6
Review Set Temperature
Compressor Protection Feature
Low Battery Detection and Replacement
cont.
Builder Series
Non-Programmable Thermostats
Single Stage 1 Heat / 1 Cool
Conventional and Heat Pump
Multi-Stage 2 Heat / 1 Cool
Conventional and Heat Pump
Always turn off power to the air conditioning or heating system prior to
installing, removing, cleaning or servicing thermostat.
This thermostat is a dual power thermostat and either requires 24 Volts AC
Power or two (2) properly installed “AA” alkaline batteries for normal
operation and control of the heating or cooling system. Refer to “Low Battery
Detection and Replacement” section for more information.
This thermostat should only be used as described in this manual. Any other
use is not recommended and will void the warranty.
Specifications
Installation
Testing Your New Thermostat
Programming User Settings
Temperature Adjustment
Additional Operation
Features
Battery Replacement
Troubleshooting
Wiring Diagrams
1
2
3
4
5
6
7
8
9
1
Specifications
• Electrical Rating: 24 Volt AC (18-30 Volt AC)
1 amp maximum load per terminal
2 amp total maximum load (all terminals) (Model PSTS11NP)
3 amp total maximum load (all terminals) (Model PSTS21NP)
• Control Range: 45˚ - 90˚ F (7˚- 32˚ C)
• Accuracy: +/- 1˚ F (+/- .5˚ C)
• AC Power: 18-30 Volt AC
• DC Power: 3.0 Volt DC (2 AA Alkaline batteries included)
Model PSTS11NP: Compatibility with low voltage single stage gas, oil or
electric heating or cooling systems, including single stage heat pumps, can
also be used on 250mv to 750mv millivolt heating only systems.
Model PSTS21NP: Compatibility with low voltage multi-stage gas, oil or
electric heating or cooling systems, including multi-stage heat pumps.
Terminations, Model PSTS11NP: Rc, Rh, B, O, Y, W, G, C
Terminations, Model PSTS21NP: R, O, B, C, Y1, E/W1, G, W2
1
Specifications
cont.
Installation
2
1. Always turn off power to the air conditioning or heating system prior to
removing existing thermostat.
2. Remove the cover of your old thermostat and locate the wire terminals.
Do not remove wires from terminals yet.
3. Using small pieces of masking tape, label wires prior to removal from
terminals. Use the chart below to determine the new terminal designations
for your new thermostat.
Installation
2
cont.
NOTE: If installing this thermostat in a new installation, locate the thermostat
4 to 5 feet above the floor in accordance with applicable building codes. Install
the thermostat in a location that provides good airflow characteristics and avoid areas
behind doors, near corners, air vents, direct sunlight or heat generating devices.
Installation in these areas could impact thermostat performance.
Wiring must conform to all building codes and ordinances as required by local
and national code authorities having jurisdiction.
1. Turn off power to the air conditioning or heating system prior to
installing thermostat.
2. Place system switch on front of thermostat to OFF position.
3. Place fan control switch on front of thermostat to AUTO position.
4. Remove front of thermostat body from sub-base by pressing release latch.
5. Place the thermostat sub-base against wall in the desired thermostat location.
6. Guide thermostat wires through hole in sub-base. Continue to hold
against wall.
7. Mark placement of mounting holes as appropriate and drill using a 3/16"
drill bit.
8. Gently tap supplied plastic anchors into the holes in the wall.
9. Place the thermostat sub-base against the wall in the desired location,
making sure the mounting holes are aligned and the thermostat wires are
inserted into the opening in sub-base.
10. Fasten sub-base to wall using supplied screws.
11. Connect wires to quick wiring terminal block using the new terminal
designations. See section 9.
12. Make sure all of the wire connections are secure and not touching any other
terminal to prevent electrical shorts and potential damage to the thermostat.
13. Turn the front thermostat body over, exposing the rear view of the
circuit board.
14. Locate the internal ˚F /˚ C switch on the circuit board. Using your fingers,
flip the switch toward the preferred temperature ˚F / ˚C scale.
15. Locate the internal fan option switch, HG (Gas) / HE (Elec) on the circuit
board. This switch controls the heating system fan delay. Select gas for gas
or oil fired systems. This will allow the furnace to run for a few seconds
before initiating the fan. Select electric for systems with electric furnace
elements that require the fan to come on immediately. Using your fingers,
flip the switch toward HG (Gas) or HE (Elec).
NOTE: For heat pump systems, the fan option switch should be set according to
the second stage heating system type.
16. Locate the internal NORM / HP switch on the circuit board. This switch
configures the thermostat for conventional (NORM) heating and cooling
systems or heat pump (HP) systems. Using your fingers, gently flip the
switch toward NORM or HP.
17. Attach front body of thermostat to sub-base of thermostat, being careful
to align the terminal pins on the front body with the terminal block on
the sub-base.
18. Open front thermostat door and open battery compartment door.
19. Install two new "AA" alkaline batteries. Locate the positive (+) ends of the
batteries and match them with the positive (+) terminals located in the
battery compartment. Close battery compartment.
20. Restore system power so you can test installation.
Installation
2
cont.
Testing Your New Thermostat
3
Do not short (or jumper) across terminals on the gas valve or at the heating or
cooling system control board to test the thermostat installation. This could
damage the thermostat and void the warranty.
Do not select COOL mode if the outside temperature is below 50˚ F (10˚ C).
This could damage the controlled cooling system and cause personal injury.
This thermostat includes an automatic compressor protection feature to
avoid potential damage to the cooling system from short cycling. This
thermostat automatically provides a 5-minute delay after turning off the
cooling or heating system output to protect the compressor.
NOTE: Test your thermostat prior to programming any user settings. Pressing
the RESET button will erase any user entries previously programmed and return them
to their default values.
1. Place the system switch in the HEAT position.
2. Press the button on the keypad until the set point temperature setting is a
minimum of 3 degrees higher than the current room temperature. The heating
system should start within several seconds. The fan may not turn on
immediately due to the heating system built-in fan delay.
3. Place the system switch in the OFF position. The heating system should stop
within several seconds with conventional heating or cooling systems. On heat
pump systems you must wait 5 minutes for the automatic compressor short
cycle protection period to expire, or press the RESET button to bypass this
feature for initial testing purposes. Pressing the RESET button will erase any
user program settings.
4. Place the system switch in the COOL position.
5. Press the button on the keypad until the set point temperature is a minimum
of 3 degrees lower than the current room temperature.
6. The cooling system should start within several seconds. Place the system
switch in the OFF position. The cooling system should stop within a few seconds.
7. Place the fan switch in the ON position. The system blower should start.
8. Place the fan switch in the AUTO position. The system blower should stop.
Programming User Settings
4
The default settings for the first and second stage differentials are compatible
with most systems and applications. This is normally set at time of installation and
usually does not require any modification under normal operating conditions. If you
feel that your system is turning on too often, simply follow the instructions below.
NOTE: The first and second stage differential settings are the same for both the
heating and cooling systems.
Setting First Stage Differential
The default setting is 0.5˚ F (0.25˚ C). The room temperature must change .5˚ F
(0.25˚ C) from the set point temperature before the thermostat will initiate the system
in heating or cooling.
1. In normal operating mode, press and hold the and
buttons at the same time for 3 seconds. LCD display will
show "SET D1 x˚", where "x" equals the ˚F / ˚C differential
setting. This is the current first stage differential setting.
2. Press the or buttons to set the first stage differential
to your desired setting of .5˚, 1˚, or 2˚ F (.2, .5˚ or 1.0˚ C).
NOTEMODEL PSTS11NP: Once you have finished setting the first stage
differential, you can wait 5 seconds and the thermostat will return to the normal
operating mode. Or you can press both the and buttons at the same time to
return to normal operating mode.
NOTEMODEL PSTS21NP: If you do not wish to change the second stage
differential, you can wait 5 seconds and the thermostat will automatically return
to the normal operating mode. Otherwise, you can press both the and buttons
at the same time to return to normal operating mode.
Programming User Settings
The default setting is 2˚ F (1.0˚ C). The room temperature
must change 2˚ F (1.0˚ C) in addition to the first stage
differential setting before the thermostat will initiate the
second stage of the system in heating.
3. Press and hold the and buttons at the same time
again and the LCD display will show "SET D2 x˚", where "x" equals the ˚F / ˚C
differential setting. This is the current second stage differential setting.
4. Press the or buttons to set the second stage differential to your desired
setting of 2˚, 3˚, 4˚, 5˚ or 6˚ F (1˚, 1.5˚, 2˚, 2.5˚ or 3˚ C).
NOTE – MODEL PSTS21NP: Once you have finished setting the second stage
differential, you can wait 5 seconds and the thermostat will return to the normal
operating mode. Or you can press both the and buttons at the same time to return
to normal operating mode.
NOTE: To erase all user program settings, gently press the RESET button using a
paper clip or a small pencil tip. This will return all thermostat settings to their
default values, erasing all program settings entered by the user.
Temperature Adjustment
1. Press and hold the or button. The current set point
temperature will be displayed in place of the current
room temperature, and the indicator SET will be displayed.
2. The display will return to normal operating mode when
the or buttons are released. The SET indicator will
turn off, indicating that the current temperature shown in the display is the
room temperature.
Changing Set Temperature
1. Press and hold the or button for more than 1 second.
The entire display will flash once and the SET indicator
will be flashing. Release the or button and press
the or button again to adjust the set temperature.
2. The display will return to normal operating mode after 5
seconds, or you can press both the and buttons at
the same time to return to normal operating mode.
3. The SET indicator will turn off in the display, indicating
that the current temperature shown in the display is the
room temperature.
This thermostat includes an automatic compressor protection feature to avoid
potential damage to the system from short cycling. This thermostat automatically
provides a 5-minute delay after turning off the cooling system output to protect
the compressor. This protection is also present in the heat mode of operation on
heat pump systems to protect the compressor.
NOTE: The installer can bypass the compressor protection feature by pressing the
RESET button. This will erase all user program settings, returning all settings to
their default values. This should only be used during installation for testing
purposes or to reset a thermostat to regain normal operation.
Additional Operation Features
6
MODEL
NOTE: This thermostat has separate heating and cooling set points, which
can be reviewed or changed by selecting either HEAT or COOL with the
system switch.
NOTE: If the thermostat was powered (batteries installed) prior to accomplishing
steps 14 through 16, you will need to reset the thermostat to register thermostat
switch configurations prior to programming any user settings. Gently press
the RESET button on the front of the thermostat using a paperclip or a small pencil
tip.
NOTE – MODEL PSTS21NP: If the thermostat is
configured for a conventional system and the system
switch is in the EMER position, the unit will still
function in a conventional 2 stage HEAT mode, but
the display will flash NO AUX SET.
Before Installing, Programming or Operating,
PLEASE READ ALL INSTRUCTIONS
This dual power thermostat requires two (2)
new, properly
installed “AA” Alkaline batteries
to provide proper thermostat
power when 24 volt AC power fails or is not connected to
the
thermostat. When the batteries start to become
too weak
to provide proper operation, the thermostat will begin to
display a 3 stage low battery indicator.
Low Battery Stage Battery Indicator Duration Action
Stage 1 Solid 0-30 Days Replace Batteries
as Soon as Possible.
Stage 2 Flashes Every 31-60 Days Replace Batteries
2 Seconds Immediately to
Provide Proper
Operation.
Stage 3 Flashes Every 61-90 Days Replace Batteries
1 Second Urgently to
Provide Proper
Operation.
The 3 stage low battery indicator is provided to inform the user when the
batteries require immediate attention. We recommend replacing the
batteries as soon as the low battery indicator appears. If the batteries are
not replaced after the low battery indicator first appears, the thermostat
may not provide proper heating or cooling system operation.
Even if the low battery indicator does not appear, the batteries should be replaced
at
least once a year, or if you plan on leaving the premises for over a month.
This dual power thermostat can be powered from 24 volts AC or battery power.
To determine if 24 volt AC power is connected to the thermostat, refer to the
installation and wiring diagram section. If you cannot determine how this
thermostat is powered, call a professional service technician to determine the
type of installation and the proper operation of your system.
Non-Volatile Memory
In the event of a power failure, the Non-Volatile Memory feature allows all settings
to be recovered, eliminating the need to reset temperature and differential settings.
When AC power is restored after an outage or batteries are reinserted, all settings
are retrieved from memory and reinstated.
4
5
STORE THIS BOOKLET FOR FUTURE REFERENCE
7
8
9
PSTS11NP: Single Stage Heat Pump System
Compressor
Control
This warranty gives you specific legal rights and you may also have other rights that vary from state
to state or province to province. Answers to any questions regarding our limited warranty may be
obtained by writing to our warranty facility.
Warranty Facility: PROSELECT Warranty Center
2215 Cornell Avenue
Montgomery, IL 60538
cont.
cont.
Troubleshooting
8
Symptom: OFF is shown in thermostat display and heating or
cooling system will not start.
Potential Solution: This indicates that the system is turned
off at the thermostat. The thermostat must be in HEAT or
COOL mode of operation to control the heating or cooling
system. Move the system selector switch to the HEAT or
COOL position.
Symptom: Thermostat display is blank.
Potential Solution: It is possible that AC power is not present at the thermostat, and/or
the batteries are drained. Check fuse, circuit breaker and thermostat wiring as appropriate
to verify AC power is available. Replace batteries before reprogramming thermostat. See
Section 7. If AC power is present, call a professional service technician to verify
thermostat and system performance.
Symptom: HI is shown in the thermostat display.
Potential Solution: The temperature sensed by the
thermostat is higher than the 99˚ F (37˚ C) upper limit of the
thermostat’s display range. The display will return to normal
after the sensed temperature lowers within the 40˚ to 99˚ F
(4˚ to 37˚ C) display range. Turn on the cooling system or use
other methods to lower the temperature accordingly.
This condition could occur from the system being turned off during an exceptionally warm
period or upon installation when the thermostat has been stored for a long period of time
in a warm vehicle or location prior to being installed.
Symptom: NO AUX SET is shown in the thermostat display.
(PSTS21NP only)
Potential Solution: The thermostat (PSTS21NP only) is
configured for a conventional system, and the system switch is
in the EM HEAT position. The unit will still function in a
conventional 2 stage HEAT mode, but the display will flash
NO AUX SET. Move the system switch to the HEAT position.
Symptom: LO is shown in the thermostat display.
Potential Solution: The temperature sensed by the
thermostat is lower than the 40˚ F (4˚ C) lower limit of the
thermostat’s display range. The display will return to normal
after the sensed temperature rises within the 40˚ to 99˚ F
(4˚ to 37˚ C) display range. Turn on the heating system to raise
the temperature as needed for comfort within the room.
This condition could occur from the system being turned off during a cold weather period
or upon installation when the thermostat has been stored for a long period of time in a
cold vehicle or location prior to being installed. The thermostat should be allowed to warm
up prior to installation to allow proper heating control once installed.
Symptom: Cannot program a set point temperature higher than 90˚ F (32˚ C).
Potential Solution: This is above the normal thermostat temperature setting range of 45˚
to 90˚ F (7˚ to 32˚ C).
Symptom: Fan continues to run whether the system is on or off.
Potential Solution: Check that the fan control switch is in the AUTO position. This will
allow the fan to run only when the heating or cooling system is turned on and running.
Check thermostat wiring to make sure that the fan control wiring is connected to the
correct terminals on the wiring block. See Section 9.
Troubleshooting
8
Symptom: The room is too warm or too cold.
Potential Solution: See Section 5. Review current set point and change as necessary.
Symptom: HEAT or COOL is flashing, but the system is not running.
Potential Solution: The thermostat is telling the heating or cooling system to run, but the
system is not responding. You may need to call your local heating and air conditioning
contractor.
Wiring Diagrams
Rc Rh
G
Factory Installed
Jumper
PSTS11NP: Single Stage Conventional Systems (Single Transformer)
WYB O
Heat
Control
Fan
Control
Cool
Control
NOTES: 1. Transformer common not required for battery-only operation of
thermostat. 2. For heating or cooling only system, ignore opposite connection. 3. For
2-wire 24 Volt AC or 250 mV - 750 mV millivolt heating systems, ignore cooling
connection and fan control.
C
Transformer Common
(See NOTE 1)
Wiring Diagrams
9
NOTE: Transformer common not required for battery-only operation of thermostat.
Transformer Common
(See NOTE 1)
cont.
Wiring Diagrams
9
R O
Reversing Valve
(Active in Cooling
- See NOTE 3)
B Y1
G W2
Transformer Common
(See NOTE 1)
1st Stage
Compressor
Contact
Emergency
Heat Control
2nd Stage
Heat Control
Fan Control
24 VAC
See NOTE 2
PSTS21NP: Multi-Stage Heat Pump Systems
NOTES: 1. Transformer common not required for battery-only operation of thermostat.
2. Jumper is required to use Auxiliary Heat for both Second Stage and Emergency Heat on
units without separat e Emergency Heat and Auxiliary Heat terminals. 3. For units
requiring reversing valve to be energized during heating, connect reversing valve to B
terminal. For units requiring reversing valve to be energized during cooling, connect
reversing valve to O terminal.
Reversing Valve
(Active in Heating
- See NOTE 3)
C E/W1
(See NOTE)
Transformer Common
R Y1 E/W1 W2GO B C
1st Stage
Compressor
Control
1st Stage
Heat Control
Fan
Control
2nd Stage
Heat Control
24 VAC
Neutral
120 VAC
Hot
PSTS21NP: Conventional Systems (Single Transformer)
NOTE: Transformer common not required for battery-only operation of thermostat.
10
9
PSTS11NP, PSTS21NP: 2 YEAR LIMITED WARRANTY
Ferguson Enterprises, Inc. warrants each new PROSELECT thermostat against any defects that
are due to faulty material or workmanship. This warranty and our liability does not apply to
batteries, nor does it include damage to merchandise or the thermostat resulting from accident,
alteration, neglect, misuse, improper installation or any other failure to follow PROSELECT
installation and operating instructions. This limited warranty applies for the duration of the
warranty period from the original date of purchase by a professional service technician.
Ferguson Enterprises, Inc. agrees to repair or replace at its option any PROSELECT thermostat
under warranty provided it is returned postage prepaid to our warranty facility in a padded
carton within the warranty period, with proof of the original date of purchase and a brief
description of the malfunction. This limited warranty does not include the cost of removal or
re-installation.
PF9002433PK
PSTS11NP
LIMITED
WARRANTY
Thermostats
Additional Operation Features
cont.
6
COOL
Troubleshooting
8
Notes
11
Battery Replacement
7
Status Indicators
HEAT: This will turn on whenever the system switch
is in the HEAT mode. “HEAT” will flash when the
heating system is running.
COOL: This will turn on whenever the system switch
is in the cool mode. “COOL” will flash when the
cooling systems is running.
AUX (PSTS21NP ONLY): This will turn on
when the auxiliary (second stage) of heating is active.
The auxiliary stage of heating is usually the least
economical stage of heat and typically runs when the
first stage of heatcannot keep up with the temperature
demand.
NOTE: AUX is also displayed when the system switch is
in the Emergency (EMER) Mode.
Replacing the Batteries
1. Open front cover and locate the battery compartment door.
2.
Gently remove the two "AA" alkaline batteries located in the battery compartment.
3. Install two new "AA" alkaline batteries into battery compartment. Make sure to
match the positive (+) ends of the batteries with the positive (+) terminals located in
the battery compartment.
4. Close battery compartment. The low battery indicator should not appear
in the display.
Symptom: Thermostat does not turn on heating or cooling system.
Potential Solution: Check to see if OFF is shown in display. This indicates that the
system is turned off at the thermostat. Move system selector switch to HEAT or COOL
position. After the compressor short cycle protection 5-minute period expires, the system
should start. Compressor protection feature may be in effect due to compressor short
cycle conditions. See Section 6. Heating or cooling system may be malfunctioning.
Call a professional service technician immediately to verify system operation.
Symptom: Thermostat turns on heating instead of cooling, or cooling instead of heating.
Potential Solution: Check thermostat wiring to make sure the heating and cooling stages
are connected to the correct terminals on the wiring block. See Section 9.
Symptom: Thermostat turns heating or cooling system on too often or not often enough.
Potential Solution: Increase or decrease temperature differential settings as appropriate
to provide the desired performance level. See Section 4.
Symptom: Low battery indicator is blinking in thermostat display.
Potential Solution: Replace batteries immediately to maintain proper system operation.
See Section 7.
24 VAC
Neutral
120 VAC
Hot
B
Reversing
Valve (Active in
Cooling - See
NOTE 2)
O W
C
24 VAC
Reversing
Valve (Active in
Heating - See
NOTE 2)
Y G
Rc Rh
Factory Installed
Jumper
Fan
Control
Neutral
120 VAC
Hot
Neutral
120 VAC
Hot
NOTES: 1. Transformer common not required for battery-only operation of
thermostat. 2. For units requiring reversing valve to be energized during heating, connect
reversing valve to B terminal. For units requiring reversing valve to be energized during
cooling, connect reversing valve to O terminal.
24 VAC
120 VAC
Neutral
Hot
Cooling
Heating
120 VAC
Neutral
Hot
24 VAC
C
Rc Rh B
Remove
Factory Installed
Jumper
PSTS11NP: Single Stage Conventional Systems (Dual Transformer)
O Y W G
Heat
Control
Cool
Control
Fan
Control
Transformer Common
(See NOTE)
PSTS11NPPSTS11NP
2215 Cornell Avenue Montgomery, IL 60538
Phone 630.844.1968 Fax 866.268.9994
Contact: Vicky Bohler • vbohler@braeburnonline.com
File:
PSTSNP-100-001.ai
Date: 04.07.10
NOTE: If changes are required to this file, please
notify Braeburn Systems BEFORE making them.
Size: 26.25”W x 8”H, folds to 3-3/4”W x 4”H
(666.75mm x 203.2mm, folds to 95.25mm x 101.6mm)
Please make sure warranty page is on back when folded.
Ink: 1 color, Black, 2 sides. Front and back bleeds
Stock: Use existing weight and color (white).
NOTE: Blue keylines do not print.
IMPORTANT - REDUCE THIS ARTWORK 68% BEFORE PRINTING.
Old Terminal from
Existing Thermostat
New Terminal for
New Thermostat
(PSTS11NP)
New Terminal for
New Thermostat
(PSTS21NP)
Terminal
Description
V or Rc Rc Cooling
Transformer
M, 4, Rh, or R Rh Heating
Transformer
R, V-VR or VR-R R 24 VAC
B B B Reversing Valve
(Heating)
O O O Reversing Valve
(Cooling)
Y, Y1 or M Y Y1 Cooling or
Compressor for
HP System
E, H, W, or 4 W E/W1 1st Stage Heat
or Emergency Heat
G or F G G Fan Control
C, X or B C C 24 VAC Common
4. After labeling and removing all wires from terminals, unscrew the existing
thermostat sub-base from wall. Secure wires to prevent them from slipping
into the hole in the wall.
NOTEMODEL PSTS11NP: This thermostat is designed for use with 24 Volt-AC
low voltage single stage gas, oil or electric heating or cooling systems, including
single stage heat pumps and can also be used on 250mv to 750mv millivolt heating
only systems. Do not use this thermostat on applications with voltages above 30
Volts AC.
NOTEMODEL PSTS21NP: This thermostat is designed for use with 24 Volt-AC
low voltage multi-stage gas, oil or electric heating or cooling systems, including
multi-stage heat pump systems. Do not use this thermostat on applications with
voltages above 30 Volts AC.
Function Status After Reset
Operation Mode Normal Operating Mode
Room Temperature 70˚ F (21.0˚ C), to be
renewed within 5 seconds
Set Point Temperature According to system switch
Heat or Off: 62˚ F (17.0˚ C)
Emergency Heat (PSTS21NP only):
62˚ F (17.0˚ C)
Cool: 85˚ F (29.0˚ C)
Temperature Scale ˚F or ˚C dependent on switch setting
Low Battery Warning Off, to be renewed within 5 seconds.
Off if 24V is present
1st Stage Differential 0.5˚ F (0.25˚C)
2nd Stage Differential 2˚ F (1.0˚ C)
Short Cycle Protection Timer Reset
Output Relays Off
PSTS11NP
MODEL
PSTS21NP
Customer Sevice: 1-877-309-7959
©2010 Ferguson Enterprises, Inc. All Rights Reserved. U.S. Patent 7,438,469 and other patents pending. PSTSNP-100-001