ProSelect Force Hot Water Oil Boiler Spec Sheet
Technical Information
• Fully packaged sectional oil boiler
• Limited lifetime warranty on heat exchanger, one year manufacturer’s
warranty on parts
• Tridicator temperature/pressure gauge
• ASME relief valve (30 PSI)
• Drain valve
• Fuel pump
• Electronic ignitor
• Made in U.S.A.
Additional Standard Features
Model*
Burner Capacity
DOE
Heating
Capacity
(MBH)
2
Net
AHRI
Ratings
(MBH)
3
AFUE
(%)
Dimensions (Inches)
Ship
Weight
(lbs.)
Tankless
DHW*
(GPM)
Replacement
Nozzle
Input
(GPH)
Input
(MBH)
1
A B
Flue
Collar
C ALT1*
FORCEVFO-3-075 0.75 105 92 80 87.0 17
3
/8 8
1
/4 5
7
/8 560 3.00 FORCEVF03E —
FORCEVFO-3-100 1.00 140 122 106 86.3 17
3
/8 8
1
/4 5
7
/8 560 3.25 FORCEVF03E** 0.85 x 60B
FORCEVFO-4-120 1.25 168 148 129 87.0 22
3
/8 10
7
/8 6
7
/8 680 3.75 FORCEVF04E —
FORCEVFO-4-150 1.50 210 182 158 86.0 22
3
/8 10
7
/8 6
7
/8 680 4.00 FORCEVF04E** 1.25 x 60B
FORCEVFO-5-175 1.75 245 214 186 86.4 27
3
/8 13
3
/8 7
7
/8 800 4.25 FORCEVF05E —
FORCEVFO-5-190 1.90 266 231 201 86.1 27
3
/8 13
3
/8 7
7
/8 800 4.75 FORCEVF05E** 1.50 x 45B
Minimum chimney requirements: 8”w x 8”d x 15’h
* Tankless coil is optional, for model numbers with tankless coil, add a “T” after “FORCEVFO” (eg: FORCEVFOT-5-190); “ALT1” column numbers
for boilers featuring tankless coils, add “T” as a suffix (eg: FORCEVFO3ET)
** Requires field purchase and installation of Hago or Delevan replacement nozzle
(1) MBH refers to thousands of BTU per hour
(2) Based on standard test procedure prescribed by the United States Departement of Energy at combustion conditions of 13.0% CO2
(3) Net AHRI Ratings are based on piping and pickup allowance of 1.15 for water
A
S
M
E
H
RELIEF VALVE
FLAME
OBSERVATION
PORT
FLUE
COLLAR
‘A’
‘B’
‘C’
DIA.
BUILT-IN DOMESTIC
WATER HEATER W/
3/4” CONNECTIONS
BOILER CONTROL
OIL BURNER
W/ PRIMARY
CONTROL
TEMP/PRESSURE
GAUGE
SUPPLY
24
5
8
“
14
1
2
“
12
1
4
“
3
5
8
“
2
1
8
“
1
1
2
“
3
3
4
“
5“
1
3
8
“
RETURN
31
5
8
“
1
1
2
“
DRAIN VALVE
BURNER SWING DOOR
CLEARANCE (OPEN 90°)
FLOOR
LINE
SEE NOTE 2
FRONT VIEW RIGHT SIDE VIEW
3
1
2
“
11”
9”
THE
NEW YORKER