ProSelect Force Steam Gas Boiler Installation Manual

21
21
106324-04 - 4/18
16) Checkthemanifoldpressureandadjustifnecessary.Todothis,usethefollowingprocedure:
a) Connectamanometertotheinletpressuretaponthegasvalve(seeFigure16).
b) Checktheinletpressurewithallgasappliancesonandoff.Theinletpressureattheboilermustbewithinthe
followinglimitsregardlessofwhatcombinationofappliancesisring:
InletPress(inchesw.c.) NaturalGas LPGas*
Min.  5.0 11.0
Max.  14.0 13.0
Iftheinletpressurefallsoutsideoftheselimits,ndandcorrectthecauseoftheproblembeforeproceeding
further.
c) Connectamanometertothemanifold(outlet)pressuretaponthegasvalve(seeFigure16).
d) Readthemanifoldpressure.Itshouldbesetat:
NaturalGas LPGas*
ManifoldPress.(inchesw.c.) 3.5 10.0
e) Ifamanifoldpressureadjustmentisneeded,maketheadjustmentbyturningthepressureregulator(seeFigure
16)screwclockwisetoraisethepressureandcounterclockwisetoreducethepressure.Ifamanifoldpressure
adjustmentismade,recheckthelinepressuretobecertainthatitisstillwithinacceptablelimits.Replacethecover
screwontheregulator.
*SeePre-InstallationSection,Number5ofofthismanualforGasConversionKits.
WARNING
FAILURE TO FOLLOW THE FOLLOWING PROCEDURE EXACTLY COULD RESULT IN OVER-
FIRING OF THE BOILER AND A CARBON MONOXIDE HAZARD.
FIGURE 13: INTERMITTENT IGNITION PILOT BURNER FLAME
XI. System Start-up (continued)