ProSelect Force Hot Water Oil Boiler Installation Manual

7
106346-06 - 8/19
FORCE
Installation, Operating & Service Manual
Boiler Model
Dimensions See Figure 1
Water Content -
Gallons
Heat Transfer
Surface Area -
Sq. Ft.
Actual Shipping
Weight (LB.)
“A” “B” “C”
FORCEOL084-
E/115-E
17” 24” 5” 7.70 13.29 475
FORCEOL140-E 23” 24” 6” 11.08 20.29 567
FORCEOL182E 29” 30” 6” 14.46 27.29 660
NOTE: 1. Maximum Working Pressure: Water: 30 PSI Shipped From Factory (Standard),
50 PSI Optional
Boiler Model
Burner Capacity
Minimum Chimney
Recommendations
Direct Vent System
GPH MBH
Round
In. Dia.
Rectangle
In. x In.
Height
Ft.
Kit
Part Number
Vent Connector
Dia. Inch
FORCEOL084-E 0.60 84 6 8 x 8 15 N/A N/A
FORCEOL115-E 0.80 115 6 8 x 8 15 N/A N/A
FORCEOL140-E 1.00 140 6 8 x 8 15 106401-01 5
FORCEOL182-E 1.30 182 7 8 X 8 15 106401-01 5
Figure 2A: Chimney Vent - Minimum Installation Clearances To Combustible Materials (Inches)
A. INSPECT SHIPMENT carefully for any signs of
damage.
1. All equipment is carefully manufactured,
inspected and packed. Our responsibility ceases
upon delivery of crated boiler to the carrier in
good condition.
2. Any claims for damage or shortage in shipment
must be filed immediately against the carrier by
the consignee. No claims for variances from,
or shortage in orders, will be allowed by the
manufacturer unless presented within sixty (60)
days after receipt of goods.
B. LOCATE BOILER in front of final position before
removing crate. See Figure 1.
1. LOCATE so that vent pipe connection to
chimney will be short and direct.
2. BOILER IS SUITABLE FOR INSTALLATION
ON COMBUSTIBLE FLOOR. Boiler cannot be
installed on carpeting.
3. FOR BASEMENT INSTALLATION, provide a
solid elevated base, such as concrete, if floor is
not level, or if water may be encountered on floor
around boiler.
4. PROVIDE RECOMMENDED SERVICE
CLEARANCE, if applicable, as follows:
a. Clearance from Jacket Front Panel -
24" for servicing burner
24" for flueway cleaning (FORCEOL084-E
through FORCEOL140-E).
30" for flueway cleaning (FORCEOL182-E)
b. Clearance from Jacket Left Side Panel -
19" for burner swing door, if opened fully
with burner mounted, otherwise 1" with
burner removed
12" access clearance to service rear of
boiler if right side clearance is less
than 12"
3" minimum if right side clearance is 12"
or larger to access and service rear of
boiler.
c. Clearance from Jacket Right Side Panel -
3" minimum if left side clearance is 12" or
larger to access and service rear of boiler.
d. Clearance from Jacket Rear Panel -
12" minimum for rear smokebox cleaning
(NOTE: This dimension will also be
controlled by horizontal to vertical to
horizontal smokepipe arrangement -
Chimney Vent (see Figures 2A and 13).
24" for rear smoke box cleaning and
disconnecting vent pipe from boiler
adaptor for servicing (if required) - Direct
Vent (see Figures 2B and 25).
NOTES: 1. Listed clearances comply with American National
Standard ANSI/NFPA 31, Standard for the Installation of
Oil Burning Equipment.
2. FORCE OIL boilers can be installed in rooms with
clearances from combustible material as listed above.
Listed clearances cannot be reduced for alcove or
closet installations.
3. For reduced clearances to combustible material,
protection must be provided as described in the above
ANSI/NFPA 31 standard.
18"
18"
18"
18"
24"
6"
18"18"
6" 6"