ProSelect Force Hot Water Oil Boiler Installation Manual

6
106346-06 - 8/19
FORCE
Installation, Operating & Service Manual
Boiler Model
Dimensions See Figure 1
Water Content -
Gallons
Heat Transfer
Surface Area -
Sq. Ft.
Actual Shipping
Weight (LB.)
“A” “B” “C”
FORCEOL084-
E/115-E
17” 24” 5” 7.70 13.29 475
FORCEOL140-E 23” 24” 6” 11.08 20.29 567
FORCEOL182E 29” 30” 6” 14.46 27.29 660
NOTE: 1. Maximum Working Pressure: Water: 30 PSI Shipped From Factory (Standard),
50 PSI Optional
Boiler Model
Burner Capacity
Minimum Chimney
Recommendations
Direct Vent System
GPH MBH
Round
In. Dia.
Rectangle
In. x In.
Height
Ft.
Kit
Part Number
Vent Connector
Dia. Inch
FORCEOL084-E 0.60 84 6 8 x 8 15 N/A N/A
FORCEOL115-E 0.80 115 6 8 x 8 15 N/A N/A
FORCEOL140-E 1.00 140 6 8 x 8 15 106401-01 5
FORCEOL182-E 1.30 182 7 8 X 8 15 106401-01 5
1 General Information (continued)
Table 1B: Rating Data
Table 1A: Dimensional Data (See Figure 1)