7. The system must be supported along its horizontal length every forty-eight inches or less and at all elbow locations using
suitable supports around pipes (See Illustration #2) maintaining clearance to combustibles as per table 2a / b on page 6
and/or 7.
8. The horizontal distance of the system from the appliance flue collar to the outside of the horizontal termination shall not be
greater than that specified in the appliance manufacturer’s installation instructions.
Vent Pipe Slope
All horizontally installed portions of a vent system shall have a slope (upwards for Category II, III, or IV
appliances) not less
than 1/4” (6.4 mm) every 12 inches (305 mm) to prevent collection of condensate at
any location in the vent system. This condensate shall be directed to a condensate drain installed
within the system.
TO CUT PIPE FOR SINGLE WALL ONLY
The pipe may be cut to length on the non-expanded end using aviation snips or a hacksaw with a 24 tpi blade. Make certain to
keep the cut end square & cylindrical. The cut end must be filed or sanded smooth before joining (see images 9 & 10).
Make certain to account for the correct insertion depth when measuring for a cut length of pipe.
2 INCH INSERTION DEPTH FOR DIAMETERS 3 INCH THRU 12 INCH
3 INCH INSERTION DEPTH FOR DIAMETERS 14 INCH THRU 24 INCH
i) Measure 2 inches (for diameters 3 inch thru 12 inch) or 3 inches (for diameters 14 inch thru 24 inch) from cut end
and draw a line to indicate depth insertion.
ii) Insert male end into female end to within ¼ inch of the drawn line to achieve full depth insertion.
Cut pipe joint connections not meeting the full insertion criteria can cause personal injury, death or
substantial property damage.
6 INCH SINGLE WALL SHOWN
Image 9 Image 10
Double wall pipe MUST NOT be cut. Adjustable pipe must be considered (Refer to the Double Wall Adjustable
section on page 10).
Single Wall Adjustable:
¾ The adjustable pipe is only to be installed into an adjacent pipe with a minimum length of 18 inches for the full range (13-
1/2 inch for sizes 5 inch thru 12 inch OR
12-1/2 for sizes 14 inch thru 24 inch) of adjustment.
NOTICE
WARNING!
NOTICE
NOTICE