Product manual

Chapter 4: Management with WebPAM PROe
151
Making UPS Settings
These settings control how the VessRAID subsystem detects the UPS unit and
responds to data reported by the UPS unit.
To make UPS settings:
1. Click the Subsystem icon in Tree View.
2. Click the UPS icon.
3. Click the Settings tab in Management View.
4. Perform the following actions as required:
Verify the Current UPS Communication method. See Note 1 below.
SNMP – USB connection.
Serial – USB connection.
Unknown – No connection.
Choose a Detection Setting from the dropdown menu:
Automatic – Default. If a UPS is detected when the subsystem
boots, the setting changes to Enable.
Enable – Monitors UPS. Settings changes, reports warnings, and
logs events.
Disable – Monitors UPS only.
Choose an Action Mode from the dropdown menu:
ShutDown – Shuts down the subsystem when a Threshold value is
exceeded.
None – No additional action when Threshold value is exceeded.
Type values into the Threshold fields. See Note 2 below.
Running Time Remaining Threshold – Actual time below this
value resets adaptive writeback cache to writethrough.
Warning Temperature Threshold – Actual temperature above this
value triggers a warning and logs an event.
Battery Charge Remaining Threshold – Reserve capacity below
this percentage triggers a warning and logs an event.
For UPS units with network cards, type IP address or DNS name in the
field provided. See Note 3 below.
5. Click the Submit button to apply your settings.
Notes
1. VessRAID supports multiple UPS units using network or serial connections,
but a combination of both methods.