The Enclosure command enables you to make settings for the enclosure. The
J310s is shown. The J610s is similar.
• Enclosure Critical Temperature – 51°C (123°F) to 61°C (141°F), measured
at the backplane
• Enclosure Warning Temperature – 10°C (50°F) to 51°C (123°F), measured
at the backplane
• Controller Critical Temperature – 61°C (141°F) to 71°C (160°F), measured
inside the I/O module
• Controller Warning Temperature – 10°C (50°F) to 61°C (141°F), measured
inside the I/O module
• Thermal Management – Monitors enclosure temperature, adjusts fan
speeds, displays red LED on cooling unit when a fan fails
• Automatic Shutdown – Shuts down the J310s when it reaches the enclosure
or controller critical temperature
• Minimum Fan Speed – Specifies the minimum fan speed when the J310s
reaches enclosure or controller warning temperature
To set the enclosure critical temperature to 61°C (141°F), at the cli> prompt, type
enclosure -a mod -s “enc_critical=61” and press Enter.
To enable Thermal Management, at the cli> prompt, type enclosure -a mod -s
“thermalmanager=1” and press Enter.
For this command, a 1 enables and a 0 disables.
To enable Automatic Shutdown, at the cli> prompt, type enclosure -a mod -s
“allowshutdown=1” and press Enter.