Setup guide
6201-WA-DFNT ♦ ProLinx Wireless Configure the 6201-WA-DFNT 150 Module
High Speed Wireless EtherNet/IP Gateway
Page 16 of 45 ProSoft Technology, Inc.
August 12, 2008
Producer Command Narrative for the First Command:
The first Produce command (on line 3) is as follows.
1 Send data using Unicast Mode
2 Send the data to IP Address 172.16.10.151.
3 Send 600 registers beginning at DB Register 1200.
4 Do not set a Swap Code.
5 Send the data every 100 milliseconds (producer commands must be 1/4 of
consumer commands).
6 Use an Exchange ID of 1002.
Producer Command Narrative for the Second Command:
1 Send data using Unicast Mode
2 Send the data to IP Address 172.16.10.151.
3 Send 600 registers beginning at DB Register 1800.
4 Do not set a Swap Code.
5 Send the data every 100 milliseconds.
6 Use an Exchange ID of 1003.
Note: IP Address 172.16.10.151 is the other 6201-WA-DFNT module that will be configured as a
DFNT Client.
The Consume commands perform the same function for data coming into the
module from the DFNT Client 151 once configured.
Consumer Command Narrative for the First Command:
Consume data using Unicast Mode.
1 Consume this data only from IP Address 172.16.10.151.
2 Consume 600 words and store them beginning at DB register 0.
3 Do not use a Swap Code.
4 Consume data within 400 milliseconds.
5 Only consume data with an Exchange ID of 1000.
The second line does exactly the same thing for another 600 words. However it
consumes this data into database registers beginning a register 600 and uses an
Exchange ID of 1001.
In order for these commands to work, the 6201-WA-DFNT (to be configured as a
remote Client module) must also be configured to consume data being produced
by the 6201-WA-DFNT (configured as a primary Client) into the appropriate
database registers and as well as be set up to produce data to allow the DFNT
Client 150 to consume.